B.13 u: monitors – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 342

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U5-03

(64)

PI Output

PI Output

Displays PI control output.

10 V: 100%

0.01%

U5-04

(65)

PI Setpoint

PI Setpoint

Displays the PI setpoint.

10 V: 100%

0.01%

U5-05

(7D2)

PI Differential Feedback

PI Feedback 2

Displays the second PI feedback value if differential feedback is used

(H3-oo = 16).

10 V: 100%

0.01%

U5-06

(7D3)

PI Adjusted Feedback

PI Diff Fdbk

Displays the difference of both feedback values if differential feedback is

used (U5-01 - U5-05).

If differential feedback is not used, then U5-01 and U5-06 will be the same.

10 V: 100%

0.01%

U5-30

(3000)

Time Hr Min HHMM

Time Hr Min HHMM

Displays the current time (Hours and Minutes).

No signal output

available

1

U5-31

(3001)

Date Year

Date Year

Displays the current year.

No signal output

available

1

U5-32

(3002)

Date Mo Day MMDD

Date Mo Day MMDD

Displays the current date (Month and Day).

No signal output

available

1

U5-33

(3003)

Date Week 000W

Date Week

Displays the current date of the week.

0: Sunday

0: Sunday

1: Monday

1: Monday

2: Tuesday

2: Tuesday

3: Wednesday

3: Wednesday

4: Thursday

4: Thursday

5: Friday

5: Friday

6: Saturday

6: Saturday

No signal output

available

1

B.13 U: Monitors

342

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

Advertising