Command, Motor does not rotate – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 254

Advertising
background image

Cause

Possible Solutions

Undervoltage was detected.

• Check the drive input power voltage by looking at the DC bus voltage (U1-07).
• Check all main circuit wiring.

u

Motor Does Not Rotate Properly after Pressing AUTO Button or after Entering External
Run Command

n

Motor Does Not Rotate

Cause

Possible Solutions

The drive is not in the Drive Mode.

• Check if the DRV light on the HOA keypad is lit.
Enter the Drive Mode to begin operating the motor.

Refer to The Drive and Programming Modes on page 99

.

HAND

was pushed.

Stop the drive and check if the correct frequency reference source is selected. If the operator keypad shall be the

source, the LO/RE button LED must be on. If the source is REMOTE, it must be off.

Take the following steps to solve the problem:

Push

HAND

.

Auto-Tuning has just completed.

• When Auto-Tuning completes, the drive is switched back to the Programming Mode. The Run command will

not be accepted unless the drive is in the Drive Mode.

• Use the HOA keypad to enter the Drive Mode.

Refer to The Drive and Programming Modes on page 99

.

A Fast Stop was executed and has

not yet been reset.

Reset the Fast Stop command.

Settings are incorrect for the source

that provides the Run command.

Check parameter Z1-08 (Run Command Selection).

Set Z1-08 so that it corresponds with the correct Run command source.

0: HOA keypad

1: Control circuit terminal (default setting)

2: MEMOBUS/Modbus communications

3: Option card

There is faulty wiring in the control

circuit terminals.

• Check the wiring for the control terminal.
• Correct wiring mistakes.
• Check the input terminal status monitor (U1-10).

The drive has been set to accept the

frequency reference from the

incorrect source.

Check parameter b1-01 (Frequency Reference Selection 1).

Set b1-01 to the correct source of the frequency reference.

0: HOA keypad

1: Control circuit terminal (default setting)

2: MEMOBUS/Modbus communications

3: Option card

The terminal set to accept the main

speed reference is set to the incorrect

voltage and/or current.

If the frequency reference is set at terminal A1, check parameter H3-01 for the correct signal level selection. If

terminal A2 is used, check parameter H3-09.

Refer to Input Signal Selection for Terminals A1 and A2 on page

85

.

Selection for the sink/source mode

and the internal/external power

supply is incorrect.

Check wire jumper connection between terminals SC and SP.

Frequency reference is too low.

Check the frequency reference monitor (U1-01).

Multi-function analog input is set up

to accept gain for the frequency

reference, but no voltage (current)

has been provided.

• Check the multi-function analog input settings.
• Check if analog inputs A1 or A2 are set for frequency reference gain (H3-02, H3-10 = 1). If so, check if the

correct signal is applied to the terminal. The gain and the frequency reference will be 0 if no signal is applied to

the gain input.

• Check if H3-02 and H3-10 have been set to the proper values.
• Check if the analog input value has been set properly. (U1-13 and U1-14)

OFF

was pressed when the

drive was started from a REMOTE

source.

Pressing

OFF

will decelerate the drive to stop.

• Switch off the Run command and then re-enter a new Run command.

Set o2-02 to 0 to disable

OFF

.

Motor starting torque is too low.

Refer to Motor Performance Fine-Tuning on page 220

.

Frequency reference value is too low

or the drive does not accept the value

entered.

Enter a value that is above the minimum output frequency determined by E1-09.

6.9 Troubleshooting without Fault Display

254

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

Advertising