L8: Drive Protection

n

L8-02: Overheat Alarm Level

Sets the overheat alarm (oH) detection level.
The drive outputs an alarm when the heatsink temperature exceeds the overheat alarm level. If the drive is set to continue

operation after this alarm occurs (L8-03 = 4

<1>

) and the temperature reaches the overheat fault level, the drive will trigger an

oH1 fault and stop operation.
<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.
When an output terminal is set for the oH pre-alarm (H2-oo = 20), the switch will close when the heatsink temperature rises

above L8-02.

No.

Name

Setting Range

Default

L8-02

Overheat Alarm Level

50 to 130 °C

Determined by

o2-04

n

L8-05: Input Phase Loss Protection Selection

Enables or disables the input phase loss detection.

No.

Name

Setting Range

Default

L8-05

Input Phase Loss Protection Selection

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

Enables input phase loss detection. Since measuring the DC bus ripple detects input phase loss, a power supply voltage

imbalance or main circuit capacitor deterioration may also trigger a phase loss fault (PF).
Detection is disabled if:
• The drive is decelerating.
• No Run command is active.
• Output current is less than or equal to 30% of the drive rated current.

n

L8-06: Input Phase Loss Detection Level

Sets the Input Phase Loss Detection (PF) Level.
Triggers PF fault when there is an imbalance larger than the value set to L8-06 in the drive input power voltage.
Detection Level = 100% = Voltage Class ×

No.

Name

Setting Range

Default

L8-06

Input Phase Loss Detection Level

0.0 to 25.0%

Determined by

o2-04

n

L8-07: Output Phase Loss Protection Selection

Enables or disables the output phase loss detection triggered when the output current falls below 5% of the drive rated current.

Note:

Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable this

parameter in such cases.

No.

Name

Setting Range

Default

L8-07

Output Phase Loss Protection Selection

0 to 2

1

Setting 0: Disabled
Setting 1: Fault when One Phase Is Lost

An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.