U4: maintenance monitors, For a complete list of u4 – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 340

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U3-46

(3024)

Date Month and Day at 9th

Most Recent Fault

Fault 9 MMDD

Displays the date and day when the ninth most recent fault occurred.

No signal output

available

U3-47

(3025)

Time Hours and Minutes

at 9th Most Recent Fault

Fault 9 HHMM

Displays the time when the ninth most recent fault occurred.

No signal output

available

U3-48

(3026)

Date Year at 10th Most

Recent Fault

Fault 10 YYYY

Displays the year when the tenth most recent fault occurred.

No signal output

available

U3-49

(3027)

Date Month and Day at

10th Most Recent Fault

Fault 10 MMDD

Displays the date and day when the tenth most recent fault occurred.

No signal output

available

U3-50

(3028)

Time Hours and Minutes

at 10th Most Recent

Fault 10 HHMM

Displays the time when the tenth most recent fault occurred.

No signal output

available

u

U4: Maintenance Monitors

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U4-01

(4C)

Cumulative Operation

Time

Drv Elapsed Time

Displays the cumulative operation time of the drive. The value for the

cumulative operation time counter can be reset in parameter o4-01. Use

parameter o4-02 to determine if the operation time should start as soon as

the power is switched on or only while the Run command is present. The

maximum number displayed is 65535.

Note:

This monitor is only updated every 10 operating hours.

No signal output

available

1 h

U4-02

(75)

Number of Run

Commands

RUN Cmd Counter

Displays the number of times the Run command is entered. Reset the

number of Run commands using parameter o4-13. This value will reset to

0 and start counting again after reaching 65535.

No signal output

available

1 Time

U4-03

(67)

Cooling Fan Operation

Time

Fan Elapsed TIme

Displays the cumulative operation time of the cooling fan. The default value

for the fan operation time is reset in parameter o4-03. The maximum

number displayed is 65535.

Note:

This monitor is only updated every 10 operating hours.

No signal output

available

1 h

U4-04

(7E)

Cooling Fan Maintenance

Fan Life Mon

Displays main cooling fan usage time as a percentage of its expected

performance life. Parameter o4-03 can be used to reset this monitor.

No signal output

available

1%

U4-05

(7C)

Capacitor Maintenance

Cap Life Mon

Displays main circuit capacitor usage time as a percentage of their expected

performance life. Parameter o4-05 can be used to reset this monitor.

No signal output

available

1%

U4-06

(07D6)

Soft Charge Bypass Relay

Maintenance

ChgCirc Life Mon

Displays the soft charge bypass relay maintenance time as a percentage of

its estimated performance life. Parameter o4-07 can be used to reset this

monitor.

No signal output

available

1%

U4-07

(07D7)

IGBT Maintenance

IBGT Life Mon

Displays IGBT usage time as a percentage of the expected performance

life. Parameter o4-09 can be used to reset this monitor.

No signal output

available

1%

U4-08

(68)

Heatsink Temperature

Heatsink Temp

Displays the heatsink temperature.

10 V: 100 °C

1 °C

U4-09

(5E)

LED Check

LED Oper Check

Lights all segments of the LED to verify that the display is working

properly.

No signal output

available

U4-10

(5C)

kWh, Lower 4 Digits

kWh Lower 4 dig

Monitors the drive output power. The value is shown as a 9-digit number

displayed across two monitor parameters, U4-10 and U4-11.

Example:

12345678.9 kWh is displayed as:

U4-10: 678.9 kWh

U4-11: 12345 MWh

No signal output

available

1 kWh

U4-11

(5D)

kWh, Upper 5 Digits

kWh Upper 5 dig

No signal output

available

1 MWh

U4-13

(7CF)

Peak Hold Current

Current PeakHold

Displays the highest current value that occurred during run.

No signal output

available

0.01 A

<1>

U4-14

(7D0)

Peak Hold Output

Frequency

Freq@ I PeakHold

Displays the output frequency when the current value shown in U4-13

occurred.

No signal output

available

0.01 Hz

B.13 U: Monitors

340

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual