Switches and jumpers on the control board, Figure 3.40 – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 84

Advertising
background image

When setting the frequency by analog reference from an external potentiometer, use shielded twisted-pair wires, preparing

wire ends as shown in

Figure 3.40

. Connect the shield to the ground terminal of the drive.

A

E

B

C

D

A – Drive side
B – Connect shield to ground terminal

of drive.

C – Insulation

D – Control device side
E – Shield sheath (insulate with tape)
F – Shield

Figure 3.40 Preparing the Ends of Shielded Cables

NOTICE: The analog signal wiring between the drive and the operator station or peripheral equipment should not exceed 50 meters when

using an analog signal from a remote source to supply the frequency reference. Failure to comply could result in poor system performance.

u

Switches and Jumpers on the Control Board

The control board is equipped with several switches used to adapt the drive I/Os to the external control signals.

Figure 3.41

shows the location of these switches.

Refer to Bypass and Drive Control I/O Connections on page 85

for setting instructions.

V

I

A1 A2

Jumper S1
Terminal A1/A2
Voltage/Current Selection

OFF ON

DIP Switch S2
RS-422/RS-485
Termination Resistor

V

I

FM AM

Jumper S5
Terminal FM/AM
Voltage/Current Selection

Figure 3.41 Locations of Jumpers and Switches on the Control Board

3.5 Control Circuit Wiring

84

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual