HOA Keypad Display

Error Name

oPE05

Run Command/Frequency Reference Source Selection Error

Cause

Possible Solutions

Frequency reference is assigned to an option card

(Z1-07) and an input option card is not connected

to the drive

Reconnect the input option card to the drive.

The Run command is assigned to an option card

(Z1-08) and an input option card is not connected

to the drive

HOA Keypad Display

Error Name

oPE07

Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-10 and PI functions

conflict.

Cause

Possible Solutions

At least two analog input terminals are set to the

same function (i.e., at least two of these parameters

have the same setting: H3-02 or H3-10)

Change the settings to H3-02 and H3-10 so that functions no longer conflict.

Note:

Both 0 (Frequency Reference Bias) and F (Not Used) can be set to H3-02 and H3-10

simultaneously.

The following simultaneous contradictory

settings:

H3-02 or H3-10 = C (PI Target Value) while

b5-18 = 1 (enables b5-19 as the target PI value)

Disable one of the PI selections.

HOA Keypad Display

Error Name

oPE09

PI Control Selection Fault
PI control function selection is incorrect. Requires that PI control is enabled (b5-01 = 1 or 3).

Cause

Possible Solutions

The following simultaneous contradictory settings

have occurred:
• b5-15 is not set to 0.0 (PI Sleep Function

Operation Level)

• The stopping method is set to either DC

Injection Braking or coast to stop with a timer

(b1-03 = 2 or 3)

• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).

b5-01 is set to 1, enabling PI control, but the lower

limit for the frequency reference (d2-02) is not set

to 0 while reverse output is enabled (b5-11 = 1)

Correct the parameter settings.

b5-01 is set to 3, enabling PI control, but the lower

limit for the frequency reference (d2-01) is not 0.

Parameter d2-01 is not accessible.

Correct the parameter settings.

HOA Keypad Display

Error Name

oPE10

V/f Data Setting Error

Cause

Possible Solutions

V/f pattern setting error

Set E1-03 to the pattern that fits the application.

HOA Keypad Display

Error Name

oPE11

Carrier Frequency Setting Error
Correct the setting for the carrier frequency.

Cause

Possible Solutions

The following simultaneous contradictory settings

have occurred: C6-05 > 6 and C6-04 > C6-03

(carrier frequency lower limit is greater than the

upper limit)
If C6-05 ≤ 6, the drive operates at C6-03

<1>

Correct the parameter settings.

The upper and lower limits between C6-02 and

C6-05 are contradictory