U1: operation status monitors, Refer to u1: operation status, U1 - 10 – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 336: U1 - 12

Advertising
background image

u

U1: Operation Status Monitors

No.

(Addr.

Hex)

Name

Description

Analog Output

Level

Unit

U1-01

(40)

Frequency Reference

Frequency Ref

Monitors the frequency reference. Display units are determined by o1-03. 10 V: Max frequency

0.01 Hz

U1-02

(41)

Output Frequency

Output Freq

Displays the output frequency. Display units are determined by o1-03.

10 V: Max frequency

0.01 Hz

U1-03

(42)

Output Current

Output Current

Displays the output current.

10 V: Drive rated

current

0.1 A

<2>

U1-04

(43)

Control Method

Control Method

0: V/f Control

No signal output

available

U1-06

(45)

Output Voltage

Reference

Output Voltage

Displays the output voltage.

10 V: 200 Vrms

<3>

0.1 Vac

U1-07

(46)

DC Bus Voltage

DC Bus Voltage

Displays the DC bus voltage.

10 V: 400 V

<3>

1 Vdc

U1-08

(47)

Output Power

Output kWatts

Displays the output power (this value is calculated internally).

10 V: Drive rated power

(kW)

<1>

U1-10

(49)

Input Terminal Status

Input Term Sts

Displays the input terminal status.

U1 - 10=

00000000

Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)

1
1
1
1
1
1
1

No signal output

available

U1-11

(4A)

Output Terminal Status

Output Term Sts

Displays the output terminal status.

U1 - 11=

00000000

Multi-Function

Digital Output

(terminal MD-ME-MF)

Digital Output

(terminal M1-M2)

Digital Output

(terminal M3-M4)

Multi-Function

Multi-Function

Not Used

Fault Relay

(terminal MA-MC closed

MA/MB-MC open)

1

1

1

1

0

No signal output

available

U1-12

(4B)

Drive Status

Int Ctl Sts 1

Verifies the drive operation status.

U1 - 12=

00000000

During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection

1

1

1

1
1

1

1
1

No signal output

available

U1-13

(4E)

Terminal A1 Input Level

Term A1 Level

Displays the signal level to analog input terminal A1.

10 V: 100%

0.1%

B.13 U: Monitors

336

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual