Figure 5.13 PI Feedback Loss Detection

n

b5-12: PI Feedback Loss Detection Selection

Enables and disables the feedback loss detection and sets the operation when a feedback loss is detected.

No.

Parameter Name

Setting Range

Default

b5-12

PI Feedback Loss Detection Selection

0 to 5

0

Setting 0: Digital Output Only

A digital output set for “PI feedback low” (H2-oo = 3E

<1>

) will be triggered if the PI feedback value is below the detection

level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PI feedback high” (H2-oo = 3F

<1>

) will be

triggered if the PI feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a

fault nor an alarm is displayed on the HOA keypad and the drive will continue operation. The output resets when the feedback

value leaves the loss detection range.

Setting 1: Feedback Loss Alarm

If the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low” alarm

will be displayed and a digital output set for “PI feedback low” (H2-oo = 3E

<1>

) will be triggered. If the PI feedback value

exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed and a

digital output set for “PI feedback high” (H2-oo = 3F

<1>

) will be triggered. Both events trigger an alarm output

(H1-oo = 10). The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection

range.

Setting 2: Feedback Loss Fault

If the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FbL - Feedback Low” fault

will be displayed. If the PI feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FbH - Feedback

High” fault will be displayed. Both events trigger a fault output (H1-oo = E

<1>

) and cause the drive to stop the motor.

Detection remains active when PI is disabled by digital input (H1-oo = 19).

Setting 3: Digital Output Always

Same as Setting 0, except that PI must be active and the drive must be running.

Setting 4: Alarm Always

Same as Setting 1, except that PI must be active and the drive must be running.

Setting 5: Fault Always

Same as Setting 2, except that PI must be active and the drive must be running.
<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.

n

b5-13: PI Feedback Low Detection Level

Sets the feedback level used for PI feedback low detection. The PI feedback must fall below this level for longer than the time

set to b5-14 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-13

PI Feedback Low Detection Level

0 to 100%

0%

5.2 b: Application

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

133