Z3: bypass control communication, Z3-01: serial communications protocol select, Z3-02: serial communications node select – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 211: Z3-03: serial communications baud rate select, Z3-04: serial communications parity select, Z3-05: serial communications fault select, Selects the bypass serial communications protocol, Selects the bypass serial communications speed

Advertising
background image

Setting 6: Vibration Switch

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR

ALM

ALM

BYP-VIBRATION SW

BYP-FAULTED

DRV/BYP

FB01

Vibration Switch

RLY

FWD

UB-01= 0.0A

RLY

UB-02=10000101
UB-03=00001000

DRV/BYP

LSEQ

LREF

u

Z3: Bypass Control Communication

n

Z3-01: Serial Communications Protocol Select

Selects the bypass serial communications protocol.

No.

Name

Setting Range

Default

Z3-01

Serial Communications Protocol Select

0 to 3

3

Setting 0: Modbus
Setting 1: N2
Setting 2: P1
Setting 3: BACnet

n

Z3-02: Serial Communications Node Select

Selects the bypass serial communications node address.

Note:

Each slave must be assigned a unique slave address for serial communications to work properly. Slave addresses do not need to be assigned

in sequential order, but no two slaves may share the same address.

No.

Name

Setting Range

Default

Z3-02

Serial Communications Node Select

0 to 127

1

n

Z3-03: Serial Communications Baud Rate Select

Selects the bypass serial communications speed.

No.

Name

Setting Range

Default

Z3-03

Serial Communications Baud Rate Select

0 to 8

3

Setting 0: 1200 bps
Setting 1: 2400 bps
Setting 2: 4800 bps
Setting 3: 9600 bps
Setting 4: 19200 bps
Setting 5: 38400 bps
Setting 6: 57600 bps
Setting 7: 76800 bps
Setting 8: 115200 bps

n

Z3-04: Serial Communications Parity Select

Selects the bypass serial communications parity. This setting is ignored when BACnet protocol is selected.

No.

Name

Setting Range

Default

Z3-04

Serial Communications Parity Select

0 to 2

0

Setting 0: No Parity
Setting 1: Even Parity
Setting 2: Odd Parity

n

Z3-05: Serial Communications Fault Select

Selects the action to take when a serial communications fault is detected. A serial communications fault is detected when after

last communicating, no communications occurs within the time set to Z3-06.

5.15 Z: Bypass Parameters

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

211

5

Programming