B.14 Z: Bypass Parameters

u

Z1: Bypass Control System

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Z1-01

(85C6) Initialize

Initialize

0: No init

1: Set All Def

2: Set Byp Def

3: Set Drv Def

0: No Initialize

1: Set all parameters to their default values. For drive parameters,

first issues two-wire reset, then sets individual parameter default

values.

2: Set only Bypass Controller parameters to their default values.

3: Set only Drive Controller parameters to their default values.

First issues two-wire reset, then sets individual parameter default

values.

Default: 0

Range: 0 to 3

195

Z1-02

(85C7) Password

Password

Allows and restricts access to all parameters. Setting this value

equal to the value in Z1-03 toggles access to all parameter settings

except this parameter. If the value entered to Z1-02 matches the

value entered to Z1-03, the access to all parameters is denied or

granted.

Default: —

Min.: —

Max.: —

195

Z1-03

(85C8) Password Change

Pass Chg

The value entered here is the password.

Default: 0

Min.: 0

Max.: 9999

195

Z1-05

(85CA)

Auto Transfer to

Bypass Upon Drive

Fault

Auto Xfr Byp Flt

When the drive is running and a drive fault occurs, operation will

switch to Bypass mode. When the fault is cleared, operation will

switch back to Drive mode

0: Disable

1: Enable

Default: 0

Range: 0, 1

195

Z1-06

(85CB) Power-Up Mode

Power-Up

Determines the mode of the Bypass Control upon power-up.

0: OFF

1: AUTO-DRIVE

2: HAND-DRIVE

3: AUTO-BYPASS

4: HAND-BYPASS

Default: 0

Range: 0 to 4

195

Z1-07

(85CC) Speed Reference Select Spd Ref Sel

Determines the source of the Frequency Reference sent from the

Bypass Controller to the Drive.

0: Operator

1: Analog Input

2: Bypass Serial

3: Option Board (CN5)

Default: 1

<1>

Range: 0 to 3

196

Z1-08

(85CD) Run Command Select Run Cmd Sel

Determines the source of the Auto Mode Run command used by

the Bypass Controller.

0: Operator

1: Bypass Controller Digital Input

2: Bypass Serial

3: Option Board (CN5)

Default: 1

Range: 0 to 3

197

Z1-09

(85CE) HAND Mode Drive

Speed Reference

Hand Fref

This is the speed reference used when the Drive is running in

HAND mode. Units are in Hz.

Default: 10.0
Hz

<2>

Min.: 0.0

Max.: 60.0

197

Z1-10

(85CF) Smoke Purge Preset

Frequency Reference

Smoke Purge

Sets the speed at which the drive will run when the Smoke Purge

Drive input is active.

Default: 10.0
Hz

<2>

Min.: 0.0

Max.: 60.0

198