Setting 2: Intelligent Stall Prevention

The drive adjusts the deceleration rate so the DC bus voltage is kept at the level set to parameter L3-17

<1>

. This produces the

shortest possible deceleration time while protecting the motor from stalling. The selected deceleration time is disregarded and

the achievable deceleration time cannot be smaller than 1/10 of the set deceleration time.
This function uses the following parameters for adjusting the deceleration rate:
• DC bus voltage gain (L3-20

<1>

)

• Deceleration rate calculations gain (L3-21

<1>

)

• Inertia calculations for motor acceleration time (L3-24

<1>

)

• Load inertia ratio (L3-25)
<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.

Note:

The deceleration time is not constant. Do not use Intelligent Stall Prevention in applications where stopping accuracy is a concern.

Setting 4: Overexcitation Deceleration 1

Overexcitation Deceleration 1 (increasing the motor flux) is faster than deceleration with no Stall Prevention (L3-04 = 0).

Setting 4 changes the selected decel time and functions to provide protection from an overvoltage trip.

Setting 5: Overexcitation Deceleration 2

Overexcitation Deceleration 2 slows down the motor while trying to maintain the DC bus voltage at the level set to parameter

L3-17

<1>

. This function shortens the achievable deceleration time more than by using Overexcitation Deceleration 1. Setting

5 will shorten/lengthen the decel time to maintain the L3-17

<1>

bus level.

<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.

n

L3-06: Stall Prevention Level during Run

Sets the current level to trigger Stall Prevention during run. Depending on the setting of parameter L3-23, the level is

automatically reduced in the constant power range (speed beyond base speed).
The Stall Prevention level can be adjusted using an analog input.

Refer to Multi-Function Analog Input Terminal Settings

on page 163

for details.

No.

Name

Setting Range

Default

L3-06

Stall Prevention Level During Run

30 to 150

<1>

<1>

<1> The upper limit and default for this setting is determined by L8-38.

n

L3-11: Overvoltage Suppression Function Selection

Enables or disables the overvoltage suppression function.

No.

Name

Setting Range

Default

L3-11

Overvoltage Suppression Function Selection

0, 1

0

Setting 0: Disabled

The regenerative torque limit and the output frequency are not adjusted. A regenerative load may trip the drive with an

overvoltage fault. Use this setting if dynamic braking options are installed.

Setting 1: Enabled

When the DC bus voltage rises due to regenerative load, an overvoltage fault is prevented by decreasing the regenerative

torque limit and increasing the output frequency.

5.9 L: Protection Functions

172