Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 367

Advertising
background image

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BV17

Data Set Error

0020H:bit 4

ERROR

OFF

R

BV18

Overcurrent – Gnd Flt

0021H:bit 0

OC-GF

OFF

R

BV19

Main Ckt OverVoltage

0021H:bit 1

OV

OFF

R

BV20

Drive OverLoad

0021H:bit 2

OL2

OFF

R

BV21

Drive OverHeat

0021H:bit 3

OH1-OH2

OFF

R

BV22

Fuse Blown

0021H:bit 5

PUF

OFF

R

BV23

PI Feedback Loss

0021H:bit 6

FBL

OFF

R

BV24

External Fault

0021H:bit 7

EF0-EF

OFF

R

BV25

Hardware Error

0021H:bit 8

CPF

OFF

R

BV26

Mtr Ovrld-OvrTorque

0021H:bit 9

OL1-OL3

OFF

R

BV27

OverSpeed

0021H:bit 10

OS-DEV

OFF

R

BV28

Main Ckt UnderVoltage

0021H:bit 11

UV

OFF

R

BV29

MCU Cntl Pwr Sy Err

0021H:bit 12

UV1-2-3

OFF

R

BV30

Output Phase Loss

0021H:bit 13

LF

OFF

R

BV31

Communication Error

0021H:bit 14

CE

OFF

R

BV32

Operator Disconnect

0021H:bit 15

OPR

OFF

R

BV33

Operating

002CH:bit 0

OPERATING

OFF

R

BV34

Zero Speed

002CH:bit 1

ON

OFF

R

BV35

Frequency Agree

002CH:bit 2

ON

OFF

R

BV36

Desired Freq Agree

002CH:bit 3

ON

OFF

R

BV37

Frequency Detect 1

002CH:bit 4

ON

OFF

R

BV38

Frequency Detect 2

002CH:bit 5

ON

OFF

R

BV39

Drv Startup Complete

002CH:bit 6

ON

OFF

R

BV40

Low Voltage Detect

002CH:bit 7

ON

OFF

R

BV41

Base Block

002CH:bit 8

ON

OFF

R

BV42

Frequency Ref Mode

8785H:bit 8

COM

LOCAL

R

BV43

Run Command Mode

8485H:bit 9

COM

LOCAL

R

BV44

Over Torque Detect

002CH:bit 11

ON

OFF

R

BV45

Frequency Ref Lost

002CH:bit 12

ON

OFF

R

BV46

Retry Error

002CH:bit 13

ON

OFF

R

BV47

Modbus Comms Error

002CH:bit 14

ON

OFF

R

BV48

Modbus Timeout Error

002CH:bit 15

ON

OFF

R

BV49

CRC Error

003DH:bit 0

ON

OFF

R

BV50

Invalid Data Length

003DH:bit 1

ON

OFF

R

BV51

Parity Error

003DH:bit 3

ON

OFF

R

BV52

Overrun Error

003DH:bit 4

ON

OFF

R

BV53

Framing Error

003DH:bit 5

ON

OFF

R

BV54

Timeout Error

003DH:bit 6

ON

OFF

R

BV55

<1>

Parameter Accept

0910H:bit 0

ON

OFF

W

BV56

<1>

Parameter Enter

0900H:bit 0

ON

OFF

W

BV57

Drive Comms Error

002CH:bit 15

ON

OFF

R

BV58

BYP Run Fwd CMD

8400H: bit 0

ON

OFF

C

BV59

BYP Run Rev CMD

8400H: bit 1

ON

OFF

C

BV60

Not Used BV60

ON

OFF

R

BV61

BYP Xfer to BYP CMD

8400H: bit 3

ON

OFF

C

BV62

BYP Smok Prg BYP CMD

8400H: bit 4

ON

OFF

C

BV63

BYP Smok Prg DRV CMD

8400H: bit 5

ON

OFF

C

BV64

BYP Mtr OR Sel CMD

8400H: bit 6

ON

OFF

C

BV65

BYP Mtr AND Sel CMD

8400H: bit 7

ON

OFF

C

C.6 BACnet Objects Supported

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

367

C

BACnet Communications

Advertising