Terminals, Table 5.21 – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 154

Advertising
background image

Table 5.21 Multi-Function Digital Output Terminal Settings

Setting

Function

Page

0

During Run 1

154

1

Zero Speed

154

2

Speed Agree 1

154

3

User-Set Speed Agree 1

155

4

Frequency Detection 1

155

5

Frequency Detection 2

156

6

Drive Ready

156

7

DC Bus Undervoltage

156

8

During Baseblock 1 (N.O.)

156

B

Torque Detection 1 (N.O.)

157

C

Frequency Reference Loss

157

E

Fault

157

F

Through Mode

157

10

Minor Fault

157

11

Fault Reset Command Active

157

13

Speed Agree 2

157

Setting

Function

Page

14

User-Set Speed Agree 2

157

15

Frequency Detection 3

158

16

Frequency Detection 4

158

17

Torque Detection 1 (N.C.)

157

1A

During Reverse

159

1B

During Baseblock 2 (N.C.)

159

1E

Restart Enabled

159

20

Drive Overheat Pre-Alarm (oH)

159

2F

Maintenance Period

159

37

During Run 2

159

39

Watt Hour Pulse Output

160

3D

During Speed Search

160

4C

During Fast Stop

160

4D

oH Pre-Alarm Time Limit

160

60

Internal Cooling Fan Alarm

160

100 to 160 Functions 0 to 60 with Inverse Output

160

Setting 0: During Run

The output closes when the drive is outputting a voltage.

Status

Description

Open

Drive is stopped.

Closed

A Run command is input or the drive is in deceleration or DC injection.

ON

ON

OFF

OFF

ON

OFF

Run command

Baseblock

command

Output

frequency

During Run

Figure 5.22 During Run Time Chart

Setting 1: Zero Speed

The output closes when the output frequency or motor speed falls below the minimum output frequency set to E1-09 or b2-01.

Status

Description

Open

Output frequency is above the minimum output frequency set to E1-09 or b2-01

Closed

Output frequency is less than the minimum output frequency set to E1-09 or b2-01

OFF

Output frequency

or

motor speed

Zero Speed

ON

E1-09 (Max. Output Frequency) or
b2-01 (Zero Speed Level)

Figure 5.23 Zero-Speed Time Chart

Setting 2: Speed Agree 1 (f

ref

/f

out

Agree 1)

The output closes when the actual output frequency or motor speed is within the Speed Agree Width (L4-02) of the current

frequency reference regardless of the direction.

5.8 H: Terminal Functions

154

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual