B.6 E: Motor Parameters

u

E1: V/f Pattern for Motor 1

No.

(Addr.

Hex)

Name

Description

Values

Page

E1-01

(300)

Input Voltage Setting

Input Voltage

This parameter must be set to the power supply voltage.

WARNING! Electrical Shock Hazard. Drive input voltage (not motor

voltage) must be set in E1-01 for the protective features of the drive to

function properly. Failure to do so may result in equipment damage

and/or death or personal injury.

Default: 230 V

<1>

Min.: 190
Max.: 240

<1>

145

E1-03

(302)

V/f Pattern Selection

V/F Selection

0: 50 Hz, Constant torque 1

0: 50 Hz

1: 60 Hz, Constant torque 2

1: 60 Hz Saturation

2: 50 Hz, Constant torque 3 (50 Hz base)

2: 50 Hz Saturation

3: 72 Hz, Constant torque 4 (60 Hz base)

3: 72 Hz

4: 50 Hz, Variable torque 1

4: 50 Hz VT1

5: 50 Hz, Variable torque 2

5: 50 Hz VT2

6: 60 Hz, Variable torque 3

6: 60 Hz VT1

7: 60 Hz, Variable torque 4

7: 60 Hz VT2

8: 50 Hz, High starting torque 1

8: 50 Hz HST1

9: 50 Hz, High starting torque 2

9: 50 Hz HST2

A: 60 Hz, High starting torque 3

A: 60 Hz HST1

B: 60 Hz, High starting torque 4

B: 60 Hz HST2

C: 90 Hz (60 Hz base)

C: 90 Hz

D: 120 Hz (60 Hz base)

D: 120 Hz

E: 180 Hz (60 Hz base)

E: 180 Hz

F: Custom V/f

F: Custom V/F`

E1-05 setting defines the V/f pattern

Default: F

<2>

Range: 0 to 9;

A to F

145

E1-05

(304)

Maximum Voltage

Max Voltage

Only applicable when E1-03 is set to F.

Default:

<3>

Min.: 0.0 V
Max.: 255.0 V

<1>

148

<1> Values shown are specific to 208 Vac. Double the value for 480 Vac.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is dependent on parameter o2-04, Drive Model Selection.

u

E2: Motor Parameters

No.

(Addr.

Hex)

Name

Description

Values

Page

E2-01

(030E)

Motor Rated Current

Motor Rated FLA

Sets the motor nameplate full load current in amps. Automatically set during

Auto-Tuning.

Default:

<1>

Min.: 10% of drive

rated current

Max.: 200% of
drive rated current

<2>

149

E2-03

(310)

Motor No-Load Current

No-Load Current

Sets the no-load current for the motor. Automatically set during Auto-Tuning. Default:

<1>

Min.: 0 A
Max.: E2-01

<2>

149

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> The number of decimal places in the parameter value depends on the drive model.

Refer to Defaults by Drive Model on page 351

for details.

B.6 E: Motor Parameters

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

317

B

Parameter List