H3: multi-function analog inputs – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 321

Advertising
background image

H2 Multi-Function Digital Output Settings

H2-oo

Setting

Function

LCD Display

Description

Page

37

During frequency output During RUN 2

Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial

Excitation is being performed.

Closed: Drive is running the motor (not in a baseblock state and DC Injection is

not being performed).

159

39

Watt hour pulse output Watt-hour Pulse

Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate

the kWh count.

160

3D

During speed search

During SpdSrch

Closed: Speed Search is being executed.

160

4C

During fast stop

During Fast Stop

Closed: A Fast Stop command has been entered from the operator or input

terminals.

160

4D

oH Pre-alarm time limit OH Pre-Alarm

Closed: oH pre-alarm time limit has passed.

160

60

Internal cooling fan

alarm

Fan Alrm Det

Closed: Internal cooling fan alarm

160

100 to

160

Function 0 to 60 with

inverse output

Note: A prefix of "!" is

added to represent

inverse functions on the

LCD keypad display.

Example: “!Zero speed”

Inverts the output switching of the multi-function output functions.

Set the last two digits of 1oo to reverse the output signal of that specific function.

160

u

H3: Multi-Function Analog Inputs

No.

(Addr.

Hex)

Name

Description

Values

Page

H3-01

(410)

Terminal A1 Signal Level

Selection

Term A1 Level

0: 0 to 10 V with zero limit

0: 0-10V, (LowLim=0)

1: 0 to 10 V without zero limit

1: 0-10V, (BipolRef)

2: 4-20 mA

3: 0-20 mA

Note:

Use jumper switch S1 to set input terminal A1 for current or

voltage.

Default: 0

Range: 0 to 3

160

H3-02

(434)

Terminal A1 Function

Selection

Term A1 FuncSel

Sets the function of terminal A1.

Default: 0

Range: 0 to 26

161

H3-03

(411)

Terminal A1 Gain Setting

Terminal A1 Gain

Sets the level of the input value selected in H3-02 when 10 V is input at

terminal A1.

Default: 100.0%

Min.: -999.9

Max.: 999.9

161

H3-04

(412)

Terminal A1 Bias Setting

Terminal A1 Bias

Sets the level of the input value selected in H3-02 when 0 V is input at terminal

A1.

Default: 0.0%

Min.: -999.9

Max.: 999.9

161

H3-09

(417)

Terminal A2 Signal Level

Selection

Term A2 Level

0: 0 to 10 V with zero limit

0: 0-10V, (LowLim=0)

1: 0 to 10 V without zero limit

1: 0-10V, (BipolRef)

2: 4 to 20 mA

2: 4-20 mA

3: 0 to 20 mA

3: 0-20 mA

Note:

Use jumper switch S1 to set input terminal A2 for current or

voltage input signal.

Default: 2

Range: 0 to 3

162

H3-10

(418)

Terminal A2 Function

Selection

Term A2 FuncSel

Sets the function of terminal A2.

Default: 0

Range: 0 to 26

162

H3-11

(419)

Terminal A2 Gain Setting

Terminal A2 Gain

Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input

at terminal A2.

Default: 100.0%

Min.: -999.9

Max.: 999.9

162

H3-12

(41A)

Terminal A2 Bias Setting

Terminal A2 Bias

Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is

input at terminal A2.

Default: 0.0%

Min.: -999.9

Max.: 999.9

162

H3-13

(41B)

Analog Input Filter Time

Constant

A1/A2 Filter T

Sets a primary delay filter time constant for terminals A1 and A2. Used for

noise filtering.

Default: 0.03 s

Min.: 0.00

Max.: 2.00

162

B.8 H Parameters: Multi-Function Terminals

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

321

B

Parameter List