Setting 2: Fault when Two Phases Are Lost

An output phase loss fault (LF) is triggered when two or more output phases are lost. The output shuts off and the motor coasts

to stop.

n

L8-09: Output Ground Fault Detection Selection

Enables or disables the output ground fault detection.

No.

Name

Setting Range

Default

L8-09

Output Ground Fault Detection Selection

0, 1

Determined by

o2-04

Setting 0: Disabled

Ground faults are not detected.

Setting 1: Enabled

A ground fault (GF) is triggered when high leakage current or a ground short circuit occurs in one or two output phases.

n

L8-38: Carrier Frequency Reduction Selection

Selects the operation of the carrier frequency reduction function. Reduces the carrier frequency when the output current exceeds

a certain level. This temporarily increases the overload capability (oL2 detection), allowing the drive to run through transient

load peaks without tripping.

No.

Name

Setting Range

Default

L8-38

Carrier Frequency Reduction Selection

0 to 2

Determined by

o2-04

Setting 0: Disabled

No carrier frequency reduction at high current.

Setting 1: Enabled for Output Frequencies below 6 Hz

The carrier frequency is reduced at speeds below 6 Hz when the current exceeds 100% of the drive rated current. The drive

returns to the normal carrier frequency when the current falls below 88% or the output frequency exceeds 7 Hz.

Setting 2: Enabled for Entire Frequency Range

The carrier frequency is reduced at the following speeds:
• Below 6 Hz when the current exceeds 100% of the drive rated current.
• Above 7 Hz when the current exceeds 112% of the drive rated current.
The drive uses the delay time set in parameter L8-40

<1>

and a hysteresis of 12% when switching the carrier frequency back

to the set value.
<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.

5.9 L: Protection Functions

180

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual