B.3 b: application – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 313

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

Page

b5-37

(1A2)

PI Feedback High Detection

Time

Fb High Dly Time

Sets the PI feedback high level detection delay time.

Default: 1.0 s

Min.: 0.0

Max.: 25.5

134

b5-38

(1FE)

PI Setpoint User Display

PI UsrDspMaxVal

Sets the display value of U5-01 and U5-04 when the maximum frequency is

output.

Default:

<1>

Min.: 1

Max.: 60000

136

b5-39

(1FF)

PI Setpoint Display Digits

PI UsrDspDigits

0: No decimal places

0: No Dec (XXXXX)

1: One decimal place

1: 1 Dec (XXXX.X)

2: Two decimal places

2: 2 Dec (XXX.XX)

3: Three decimal places

3: 3 Dec (XX.XXX)

Default:

<1>

Range: 0 to 3

136

b5-40

(17F)

Frequency Reference

Monitor Content during PI

Fref Mon Sel@PI

0: Display the frequency reference (U1-01) after PI compensation has been

added.

0: After PI

1: Display the frequency reference (U1-01) before PI compensation has been

added.

1: Before PI

Default: 0

Range: 0, 1

136

b5-46

(165)

PI Setpoint Monitor Unit

Selection

PI Mon Unit Sel

0: “WC

0: “WC

(Inch of water)

1: PSI

1: PSI

(Pounds per square inch)

2: GPM

2: GPM

(Gallons per minute)

3: F

3: °F

(Degrees Fahrenheit)

4: CFM

4: CFM

(Cubic feet per minute)

5: CMH

5: CMH

(Cubic meters per hour)

6: LPH

6: LPH

(Liters per hour)

7: LPS

7: LPS

(Liters per second)

8: Bar

8: Bar

(Bar)

9: Pa

9: Pa

(Pascal)

10: C

10: °C

(Degrees Celsius)

11: Mtr

11: Mtr

(Meters)

12: Ft

12: Ft

(Feet)

13: LPM

13: LPM

(Liters per minute)

14: CMM

14: CMM

(Cubic meters per minute)

Default: 0

Range: 0 to 14

136

b5-47

(17D)

Reverse Operation Selection

2 by PI Output

Output Rev Sel2

Reverse operation selection when b5-01 = 3

0: Reverse Disabled

0: 0 limit

1: Reverse Enabled

1: Reverse

Default: 1

Range: 0, 1

137

<1> Default setting is dependent on parameter b5-20, PI Setpoint Scaling.

B.3 b: Application

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

313

B

Parameter List