HOA Keypad Display

Fault Name

oPr

HOA Keypad Connection Fault
The HOA keypad has been disconnected from the drive.

Note:

An oPr fault will occur when The Run command is assigned to the keypad (Z1-07 = 0

and OFF mode has been selected).

Cause

Possible Solution

External operator is not properly connected to the

drive

• Check the connection between the operator and the drive.
• Replace the cable if damaged.
• Turn off the drive input power and disconnect the operator. Reconnect the operator and reapply

drive input power.

HOA Keypad Display

Fault Name

ov

Overvoltage
Voltage in the DC bus has exceeded the overvoltage detection level.
• For 208 V: approximately 410 V
• For 480 V: approximately 820 V (740 V when E1-01 is less than 400)

Cause

Possible Solution

Deceleration time is too short and regenerative

energy is flowing from the motor into the drive

• Increase the deceleration time (C1-02).
• Set L3-04 to 1 to enable stall prevention during deceleration. Stall Prevention is enabled as the

default setting.

Fast acceleration time causes the motor to

overshoot the speed reference

• Check if sudden drive acceleration triggers an overvoltage alarm.
• Increase the acceleration time.
• Use longer S-curve acceleration and deceleration times.
• Enable the Overvoltage Suppression function (L3-11 = 1).
• Lengthen the S-curve at acceleration end.

Ground fault in the output circuit causes the DC

bus capacitor to overcharge

• Check the motor wiring for ground faults.
• Correct grounding shorts and reapply power.

Improper parameters related to Speed Search

(including Speed Search after a momentary power

loss and after a fault restart)

• Check the settings for Speed Search-related parameters.
• Enable Speed Search restart function (b3-19 greater than or equal to 1 to 10).
• Adjust the current level during Speed Search and the deceleration time (b3-02 and b3-03

respectively).

• Perform Stationary Auto-Tuning for line-to-line resistance and then set b3-14 to 1 to enable Speed

Estimation Speed Search.

Drive input power voltage is too high

• Check the voltage.
• Lower drive input power voltage within the limits listed in the specifications.

Drive fails to operate properly due to noise

interference

• Review the list of possible solutions provided for controlling noise.
• Review the section on handling noise interference on page

257

and check the control circuit lines,

main circuit lines, and ground wiring.

Load inertia is set incorrectly

• Check the load inertia settings when using KEB, overvoltage suppression, or Stall Prevention

during deceleration.

• Adjust the load inertia ratio in L3-25 to better match the load.

Motor hunting occurs

• Adjust the parameters that control hunting.
• Set the gain for Hunting Prevention (n1-02).

HOA Keypad Display

Fault Name

ov2

Overvoltage 2
Bus voltage is boosted because the motor cable is too long.

Cause

Possible Solution

The wiring is too long

• Shorten the shielded motor cable
• Lower the carrier frequency
• Switch on the internal EMC filter if the power supply has a neutral ground

HOA Keypad Display

Fault Name

PF

Input Phase Loss
Drive input power has an open phase or has a large imbalance of voltage between phases. Detected

when L8-05 is set 1 (enabled).

Cause

Possible Solution

6.4 Fault Detection

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

235

6

Diagnostics & Troubleshooting