Z1-36

Loss of Load Bypass Time

0.0 to 300.0

1.0 s

n

Z1-37: Set Time

Changes the LCD display to time setting to set the Real Time Clock.

Note:

Setting 2 is added in bypass controller software version VST800298. Setting 2 is not available in bypass controller software versions

VST800297 and earlier.

No.

Name

Setting Range

Default

Z1-37

Set Time

0 to 2

0

Setting 0: Normal Display
Setting 1: Displays Time and Date Setting Mode
Setting 2: Reset Time

n

Z1-38: HOA Source Select

No.

Name

Setting Range

Default

Z1-38

HOA Source Select

0 to 2

0

Setting 0: Operator

The HOA keypad controls the HAND/OFF/AUTO commands.

Setting 1: Digital Inputs

The H1-oo multi-function digital input parameters control the HAND/OFF/AUTO commands.

Setting 2: Serial Communications

The serial communications protocol selected in parameter Z3-01 control the HAND/OFF/AUTO commands.

n

Z1-39: Drive/Bypass Source Select

No.

Name

Setting Range

Default

Z1-39

Drive/Bypass Source Select

0 to 2

0

Setting 0: Operator

The HOA keypad selects the Drive or Bypass as the source.

Setting 1: Digital Inputs

The H1-oo multi-function digital input parameters select the Drive or Bypass as the source.

Setting 2: Serial Communications

The serial communications protocol selected in parameter Z3-01 selects the Drive or Bypass as the source.

n

Z1-40: Auto Transfer Wait Time

Sets the length of time that the bypass controller will wait before switching to bypass when Auto Transfer is enabled and a

drive fault is detected.

No.

Name

Setting Range

Default

Z1-40

Auto Transfer Wait Time

0.0 to 300.0 s

0.0 s

n

Z1-41: HAND Speed Reference Selection

Selects the frequency reference source when in HAND Mode.

Note:

Parameter available in bypass controller software versions VST800298 and later.

No.

Name

Setting Range

Default

Z1-41

HAND Speed Reference Selection

0, 1

0

Setting 0: Parameter Z1-09

Parameter Z1-09 sets the frequency reference for the drive when in HAND Mode.

5.15 Z: Bypass Parameters

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

205