No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Z1-11

(85D0) 2-Motor AND/OR

Function Select

2-Mtr AND/OR Sel

0: Disabled (ignore digital inputs)

1: Always use only motor 1

2: Always use only motor 2

3: Always use motors 1 AND 2

4: OR function motor selected by digital input in HAND and

AUTO modes

5: OR function use motor 1 in HAND mode and motor selected

by digital input in AUTO mode

6: OR function use motor 2 in HAND mode and motor selected

by digital input in AUTO mode

7: AND/OR function motor selected (1, 2, or both) by (2) digital

inputs in HAND and AUTO mode

8: AND/OR function use motor 1 in HAND mode and motor

selected (1, 2, or both) by (2) digital inputs in AUTO mode

9: AND/OR function use motor 2 in HAND mode and motor

selected (1, 2, or both) by (2) digital inputs in AUTO mode

10: AND/OR function use motors 1 AND 2 in HAND mode and

motor selected (1, 2, or both) by (2) digital inputs in AUTO mode

Default: 0

Range: 0 to 10

198

Z1-12

(85D1) Run Delay Time

Run Delay Time

Delays the drive or bypass Run from when commanded (after

RUN, RUN ENABLE, and RUN INTERLOCK are all asserted).

Default: 0.0 s

Min.: 0.0

Max.: 300.0

198

Z1-13

(85D2) Pre-Interlock Run

Select

Pre Int Run Sel

Allows running at a preset speed starting immediately upon a Run

command, ignoring the BAS Interlock Input. The drive frequency

reference stays at this preset speed until the Run Delay time

(Z1-12) times out.

0: Disabled

1: Enable delay time only

Default: 0

Range: 0, 1

198

Z1-14

(85D3) Run Delay Frequency

Reference

Run Delay Fref

Frequency used while delaying the Run command.

Default: 60.0
Hz

<2>

Min.: 0.0

Max.: 60.0

198

Z1-15

(85D4) Interlock Wait Time

Interlck Wait

Upon entering a Run command, the damper actuator output will

be asserted. When an input is programmed for Interlock and the

time set to this parameter is reached before the Interlock input

goes active, a fault will be declared.

A setting of 0.0 will never time out.

Default: 0.0 s

Min.: 0.0

Max.: 300.0

199

Z1-16

(85D5)

Energy Savings Mode

Enable

Enrgy Savings En

0: Disable

1: Enable (Freq)

2: Enable (Freq + Cur)

Note:

Energy Savings will not function if the motor is

running in reverse.

Default: 0

Range: 0 to 2

202

Z1-17

(85D6) Energy Savings Mode

Frequency

Energy Freq

Sets the value of the drive frequency reference for use in

comparison to enter or exit Energy Savings mode.

Default: 60.0
Hz

<2>

Min.: 0.0

Max.: 60.0

202

Z1-18

(85D7) Energy Savings Mode

Output Current Level

Energy Iout Lvl

Allows system to switch when the output current rises above this

level of motor rated current for time specified in Energy Time.

Default: 0.0%

Min.: 0.0

Max.: 100.0

202

Z1-19

(85D8)

Energy Savings Mode

Frequency Reference

Deadband

Enrgy Fref Dbnd

Sets the tolerance around the drive frequency reference value

during comparisons to enter or exit Energy Savings mode

Default: 0.5 Hz

<2>

Min.: 0.0

Max.: 5.0

202

Z1-20

(85D9)

Energy Savings Mode

Output Frequency

Deadband

Energy Freq Dbnd

Sets the tolerance around the drive output frequency value during

comparisons to enter or exit Energy Savings mode.

Default: 0.5 Hz

<2>

Min.: 0.0

Max.: 5.0

203

Z1-21

(85DA)

Energy Savings Mode

Output Current

Deadband

Energy Iout Dbnd

Sets the tolerance around the drive output current value during

comparisons to enter or exit Energy Savings mode as a percentage

of motor rated current.

Default: 15.0%

Min.: 0.0

Max.: 30.0

203

Z1-22

(85DB) Energy Savings Mode

Time

Energy Time

Sets the time that the drive frequency reference and drive output

frequency must be within the set limits before transferring to

Energy Savings mode.

Default: 30 s

Min.: 10

Max.: 60000

203

B.14 Z: Bypass Parameters

344