Connecting to a network, Network cable connection, E.2 connecting to a network – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 405

Advertising
background image

E.2 Connecting to a Network

u

Network Cable Connection

Follow the instructions below to connect the bypass to a MEMOBUS/Modbus network.

Note:

Separate the communication cables from the main circuit cables and other wiring and power cables. Use shielded cables for the

communication cables and properly shielded clamps to prevent problems from electrical interference.

• With the power shut off, connect the communications cable to the bypass controller and the master. Use the terminal TB3

for MEMOBUS/Modbus.

4

Shield

SHLD

Isolated Ground Reference

IG5

Transmit/Recieve (-)

TXRX-

Transmit/Recieve (+)

TXRX+

3

2

1

TB3

Figure E.1 Serial Communications Cable Connection Terminal (TB3)

• Check or set the termination resistor selection at all slaves.

Refer to Network Termination on page 359

for slaves that are

Z1000 Bypasses.

• Apply power.
• Set parameters Z3-01 to Z3-11 needed for serial communications using the HOA keypad.
• Remove power and wait for the display on the HOA keypad to go blank.
• Reapply power.
• The bypass is now ready to begin communicating with the master.

E.2 Connecting to a Network

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

405

E

Apogee FLN Network Protocol