Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 162

Advertising
background image

0

2.0 V

10 V

100 %

Frequency
reference

-25%

H3-01 = 0

H3-01 = 1

H3-01 = 0

Analog Input

Voltage

Figure 5.35 Frequency Reference Setting by Analog Input with Negative Bias

n

H3-09: Terminal A2 Signal Level Selection

Selects the input signal level for analog input A2. Set Jumper S1 on the terminal board accordingly for a voltage input or

current input.

No.

Name

Setting Range

Default

H3-09

Terminal A2 Signal Level Selection

0 to 3

2

Setting 0: 0 to 10 V with Zero Limit

The input level is 0 to 10 Vdc. Negative input values will be limited to 0.

Refer to Setting 0: 0 to 10 V with Zero Limit on

page 160

.

Setting 1: 0 to 10 V without Zero Limit

The input level is 0 to 10 Vdc. Negative input values will be accepted.

Refer to Setting 1: 0 to 10 V without Zero Limit on

page 161

.

Setting 2: 4 to 20 mA Current Input

The input level is 4 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

Setting 3: 0 to 20 mA Current Input

The input level is 0 to 20 mA. Negative input values by negative bias or gain settings will be limited to 0%.

n

H3-10: Terminal A2 Function Selection

Determines the function assigned to analog input terminal A2.

Refer to Multi-Function Analog Input Terminal Settings on

page 163

for a list of functions and descriptions.

No.

Name

Setting Range

Default

H3-10

Terminal A2 Function Selection

0 to 26

0

n

H3-11, H3-12: Terminal A2 Gain and Bias Setting

Parameter H3-11 sets the level of the input value selected that is equal to 10 Vdc input or 20 mA input to terminal A2.
Parameter H3-12 sets the level of the input value selected that is equal to 0 V, 4 mA or 0 mA input at terminal A2.
Use both parameters to adjust the characteristics of the analog input signal to terminal A2. The setting works in the same way

as parameters H3-03 and H3-04 for analog input A1.

No.

Name

Setting Range

Default

H3-11

Terminal A2 Gain Setting

-999.9 to 999.9%

100.0%

H3-12

Terminal A2 Bias Setting

-999.9 to 999.9%

0.0%

n

H3-13: Analog Input Filter Time Constant

Parameter H3-13 sets the time constant for a first order filter that will be applied to the analog inputs.
An analog input filter prevents erratic drive control when using a “noisy” analog reference. Drive operation becomes more

stable as the programmed time becomes longer, but it also becomes less responsive to rapidly changing analog signals.

No.

Name

Setting Range

Default

H3-13

Analog Input Filter Time Constant

0.00 to 2.00 s

0.03 s

5.8 H: Terminal Functions

162

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual