3.6 Bypass and Drive Control I/O Connections

u

Input Signal Selection for Terminals A1 and A2

Terminals A1 and A2 can be used to input either a voltage or a current signal. Select the signal type using jumper S1 as

explained in

Table 3.12

. Set parameters H3-01 and H3-09 accordingly as shown in

Table 3.13

.

Refer to Switches and Jumpers

on the Control Board on page 84

for locating switch S1.

Note:

If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency

reference.

Table 3.12 Jumper S1 Settings

Terminal

Voltage Output

Current Output

Terminal A1

A2

A1

V

I

A2

A1

V

I

Terminal A2

A2

A1

V

I

A2

A1

V

I

Table 3.13 Parameters H3-01 and H3-09 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-01

Terminal A1 signal level selection

Selects the signal level for terminal A1.

0: 0 to 10 V with Zero Limit

1: 0 to 10 V without Zero Limit

2: 4 to 20 mA Current Input

3: 0 to 20 mA Current Input

0 to 3

0

H3-09

Terminal A2 signal level selection

Selects the signal level for terminal A2.

0: 0 to 10 V with Zero Limit

1: 0 to 10 V without Zero Limit

2: 4 to 20 mA Current Input

3: 0 to 20 mA Current Input

0 to 3

0

u

Terminal FM/AM Signal Selection

The signal type for terminals FM and AM can be set to either voltage or current output using jumper S5 on the terminal board

as explained in

Table 3.14

. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.

The default selection is voltage output for both terminals.

Refer to Switches and Jumpers on the Control Board on page

84

for locating jumper S5.

Table 3.14 Jumper S5 Settings

Terminal

Voltage Output

Current Output

Terminal FM

AM

FM

V

I

AM

FM

V

I

Terminal AM

AM

FM

V

I

AM

FM

V

I

Table 3.15 Parameter H4-07 and H4-08 Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H4-07

Terminal FM signal level selection

0: 0 to 10 Vdc

2: 4 to 20 mA

0, 2

0

H4-08

Terminal AM signal level selection

3.6 Bypass and Drive Control I/O Connections

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

85