E: motor parameters, E1: v/f pattern for motor 1, 6 e: motor parameters – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 145

Advertising
background image

5.6 E: Motor Parameters

E parameters cover V/f pattern and motor data settings.

u

E1: V/f Pattern for Motor 1

n

E1-01: Input Voltage Setting

Adjusts the levels of some protective features of the drive (overvoltage, Stall Prevention, etc.). Set this parameter to the nominal

voltage of the AC power supply.

NOTICE: Set parameter E1-01 to match the input voltage of the drive. Drive input voltage (not motor voltage) must be set in E1-01 for the

protective features to function properly. Failure to set the correct drive input voltage will result in improper drive operation.

No.

Parameter Name

Setting Range

Default

E1-01

Input Voltage Setting

190 to 240 V

<1>

230 V

<1>

<1> Values shown are specific to 208 Vac. Double the value for 408 Vac.

E1-01 Related Values

The input voltage setting determines the overvoltage and undervoltage detection levels, the KEB function, and the overvoltage

suppression function.

Voltage

Setting Value of E1-01

(Approximate Values)

Uv Detection Level (L2-05)

208 Vac

All settings

190 V

408 Vac

Setting > 460 V

440 V

n

V/f Pattern Settings (E1-03)

The drive uses a V/f pattern to adjust the output voltage relative to the frequency reference. There are 15 different predefined

V/f patterns (setting 0 to E) from which to select, each with varying voltage profiles, saturation levels (frequency at which

maximum voltage is reached), and maximum frequencies. Additionally, one custom V/f pattern is available (setting F) that

requires the user to create the pattern using parameters E1-04 through E1-10.

n

E1-03: V/f Pattern Selection

Selects the V/f pattern for the drive and motor from 15 predefined patterns or creates a custom V/f pattern.

No.

Parameter Name

Setting Range

Default

E1-03

V/f Pattern Selection

0 to 9; A to F

F

Setting a Predefined V/f Pattern (Setting 0 to F)

Choose the V/f pattern that best meets the application demands from the table below. Set the correct value to E1-03. Parameter

E1-05 can only be monitored, not changed.

Note:

1. Setting an improper V/f pattern may result in low motor torque or increased current due to overexcitation.
2. Drive initialization does not reset parameter E1-03.

Table 5.7 Predefined V/f Patterns

Setting

Specification

Characteristic

Application

0

50 Hz

Constant torque

For general purpose applications. Torque remains constant

regardless of changes to speed.

1

60 Hz

2

60 Hz (with 50 Hz base)

3

72 Hz (with 60 Hz base)

4

50 Hz, Variable torque 1

Variable torque

For fans, pumps, and other applications where the required

torque changes as a function of the speed.

5

50 Hz, Variable torque 2

6

50 Hz, Variable torque 3

7

50 Hz, Variable torque 4

5.6 E: Motor Parameters

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

145

5

Programming

Advertising