Wiring diagram for multiple connections, Network termination, Rs-485 interface – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 379: D.3 connecting to a network

Advertising
background image

u

Wiring Diagram for Multiple Connections

Figure C.3

explains the wiring diagrams for multiple connections using MEMOBUS/Modbus communication.

n

RS-485 Interface

CONTROLLER

1

2

3

4

+

-

SHLD

Bypass

S1

OFF

TB3

SHLD

TXRX-

TXRX+

IG5

1

2

3

4

Bypass

S1

OFF

TB3

SHLD

TXRX-

TXRX+

IG5

ON

1

2

3

4

Bypass

S1

SHLD

TXRX-

TXRX+

IG5

Bypass
Controller
Board A2

Bypass
Controller
Board A2

Bypass
Controller
Board A2

Figure D.3 Connection Diagram for Multiple Connections

Note:

Turn on DIP switch S1 on the bypass controller located at the end of the network. If S1 is missing, then an external 120 ohm resistor must

be placed across terminals TXRX+ and TXRX-. All other slave devices must have this DIP switch set to the OFF position (or if S1 is

missing, no external resistor is used).

u

Network Termination

The two ends of the MEMOBUS/Modbus network line have to be terminated with a 120 ohm resistor between the TXRX+

and TXRX- signals. The Z1000 Bypass has a built in termination resistor that can be enabled or disabled using DIP switch

S1. If a bypass is located at the end of a network line, enable the termination resistor by setting DIP switch S1 to the ON

position. Disable the termination resistor on all slaves that are not located at the network line end.

Note:

Some bypass controllers do not have DIP switch S1. If this is the case, then an external 120 ohm resistor must be placed across the

TXRX+ and TXRX- signals if the bypass controller is at the end of a network line.

D.3 Connecting to a Network

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

379

D

MEMOBUS/Modbus Communications

Advertising