Goal

Tuning Procedure

Result

Suppress long cycle oscillations

(longer than the integral time setting) Increase the integral time (b5-03)

Response

Before adjustment

After adjustment

Time

Suppress short cycle oscillations

If oscillations are a problem, reduce the

proportional gain (b5-02) or increase the PI

primary delay time (b5-08)

Response

Before adjustment

After adjustment

Time

5.2 b: Application

138

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual