2 b: application – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual
Page 138
Advertising
Goal
Tuning Procedure
Result
Suppress long cycle oscillations
(longer than the integral time setting) Increase the integral time (b5-03)
Response
Before adjustment
After adjustment
Time
Suppress short cycle oscillations
If oscillations are a problem, reduce the
proportional gain (b5-02) or increase the PI
primary delay time (b5-08)
Response
Before adjustment
After adjustment
Time
5.2 b: Application
138
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual