Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 412

Advertising
background image

Point

No.

Point

Type

Point Name

Factory

Default

(SI Units)

Engr. Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

Z1000

Parameter

91

LAO

CBL LOSS

FRQ

0

HZ

0.01

0

Z3-10

92

LAO

CBL LOSS

TMR

2

SEC

0.1

0

Z3-06

{93}

LDI

OK.FAULT

OK

1

0

FAULT

OK

UB-06 (Bit 2)

{94}

LDO

RESET

FAULT

NO

1

0

RESET

NO

{95}

LDI

DRV COMM

ERR

NO FLT

1

0

FAULT

NO FLT

{96}

LDO

EXTERNAL

FLT

OK

1

0

FAULT

OK

{97}

LDI

MF IN 5

MON

OFF

1

0

ON

OFF

UB-02 (Bit 6)

Bypass DI-7

{99}

LAI

ERROR

STATUS

0

1

0

<1> In bypass controller software versions VST800298 and later, the number of decimal places in the value depends on the bypass model. This value

has two decimal places in models Z1B1D002 to Z1B1D031 and Z1B1B001 to Z1B1B014; this value has one decimal place in models Z1B1D046
to Z1B1D273 and Z1B1B021 to Z1B1B302.

<2> Point LDI 18 displays both drive alarms and bypass alarms in bypass controller software versions VST800298 and later.
<3> Set Z2-02 to 22 (Run Enable) for point 35 to work properly.
<4> Disabled when Z3-12 is set to 0 in bypass controller software versions VST800298 and later.

E.4 APOGEE FLN Point List Summary

412

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual