6 e: motor parameters – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 146

Advertising
background image

Setting

Specification

Characteristic

Application

8

50 Hz, Mid starting torque

High starting torque

Select high starting torque when:
• Wiring between the drive and motor exceeds 150 m.
• A large amount of starting torque is required.
• An AC reactor is installed.

9

50 Hz, High starting torque

A

60 Hz, Mid starting torque

B

60 Hz, High starting torque

C

90 Hz (with 60 Hz base)

Constant output

Output voltage is constant when operating at greater than

60 Hz.

D

120 Hz (with 60 Hz base)

E

180 Hz (with 60 Hz base)

F

<1>

60 Hz

Variable torque

Used for variable torque applications. The default setting is

the same as V/f pattern Setting 7.

<1> Setting F enables a custom V/f pattern by changing parameters E1-05. When the bypass is shipped, the default values for parameter E1-05 is are

equal to predefined V/f pattern 1.

The following tables show details on predefined V/f patterns.

Predefined V/f Patterns for Models Z1B1D002 to D024 and Z1B1B001 to B011

The values in the following graphs are specific to 208 Vac. Double the values for 480 Vac.

Table 5.8 Constant Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

9

200

1.3 2.5

50

15

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

60

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 5.9 Variable Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

8

200

1.3

25

50

35

V

oltage (V)

Frequency (Hz)

0

9

200

1.3

25

50

50

V

oltage (V)

Frequency (Hz)

0

8

200

1.5

30

60

35

V

oltage (V)

Frequency (Hz)

0

9

200

1.5

30

60

50

V

oltage (V)

Frequency (Hz)

Table 5.10 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

11

200

1.3 2.5

50

19

V

oltage (V)

Frequency (Hz)

0

13

200

1.3 2.5

50

24

V

oltage (V)

Frequency (Hz)

0

11

200

1.5 3

60

19

V

oltage (V)

Frequency (Hz)

0

15

200

1.5 3

60

24

V

oltage (V)

Frequency (Hz)

Table 5.11 Rated Output Operation, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

9

15

200

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

9

15

200

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

10.2

17.3

230

1.5 3

60

V

oltage (V)

Frequency (Hz)

5.6 E: Motor Parameters

146

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual