No.

Name

Setting Range

Default

Z3-05

Serial Communications Fault Select

0 to 4

1

Setting 0: Ignore
Setting 1: Alarm Only
Setting 2: Fault with EF0

An EF0 fault will be sent to the drive.

Setting 3: Fault with EF0 and Open Contactors

An EF0 fault will be sent to the drive and the bypass contactor (K3) will be opened.

Setting 4: Alarm and run at preset speed set in Z3-10

Display AL14 alarm on operator.

n

Z3-06: Serial Communications Fault Time Select

Sets the time allowed to elapse since receiving serial communications before triggering a communications fault.
A value of 0.0 means to never time out.

No.

Name

Setting Range

Default

Z3-06

Serial Communications Fault Time Select

0.0 s to 99.9 s

2.0 s

n

Z3-07: Serial Communications Receive to Transmit Wait Time

Sets the time to delay a serial communications response to a serial communications command.

No.

Name

Setting Range

Default

Z3-07

Serial Communications Receive to Transmit Wait Time

0 to 99 ms

5 ms

n

Z3-08, Z3-09: BACnet Device Object Identifier

These parameters set the Instance Identifier of the BACnet Device Object, where Z3-08 is the least significant word and Z3-09

is the most significant word.

No.

Name

Setting Range

Default

Z3-08

BACnet Device Object Identifier 0

0 to FFFFH

1

Z3-09

BACnet Device Object Identifier 1

0 to 003FH

0

Example 1: Set Device Object Instance Identifier of “1234”.
1234 decimal is equal to 4D2H (hexadecimal).
Set Z3-08 to 4D2H and set Z3-09 to 0.
Example 2: Set Device Object Instance Identifier of “123456”.
123456 decimal is equal to 12D687H.
Set Z3-08 to D687H and set Z3-09 to 12H.

n

Z3-10: Cable Loss Pre-set Speed

Sets the frequency reference when a serial communications fault is detected and Z3-05 is set to 4.

No.

Name

Setting Range

Default

Z3-10

Cable Loss Pre-set Speed

0.0 to 60.0 Hz

0.0 Hz

n

Z3-11: Communication Fault Detection Selection

No.

Name

Setting Range

Default

Z3-11

Communication Fault Detection Selection

0 to 1

1

Setting 0: Disabled

Ignore setting in Z3-05.

5.15 Z: Bypass Parameters

212