Memobus/modbus data table, Command data, D.9 memobus/modbus data table – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 388

Advertising
background image

D.9 MEMOBUS/Modbus Data Table

The tables below list all MEMOBUS/Modbus data.

u

Command Data

It is possible to both read and write command data.

Note:

Bits that are not used should be set to 0. Refrain from writing to reserved registers.

Register No.

Contents

0000H

Reserved

0001H

Operation Commands and Multi-function Inputs
bit 0

Reserved

bit 1

Reserved

bit 2

External Fault (EF0)

bit 3

Fault Reset

bit 4

Reserved

bit 5

Reserved

bit 6

Multi-Function Input 3

bit 7

Multi-Function Input 4

bit 8

Multi-Function Input 5

bit 9

Multi-Function Input 6

bit A

Multi-Function Input 7

bit B to F

Reserved

0002H

Reserved

Reserved

0003H

V/f Gain

0004H, 0005H

Reserved

0006H

PI Target, 0.01% units, signed

0007H

Analog Output Terminal FM Setting (10 V / 4000 H)

0008H

Analog Output Terminal AM Setting (10 V / 4000 H)

0009H

Settings for Multi-Function Digital Outputs
bit 0

Multi-Function Contact Output 1 (terminal M1-M2)

bit 1

Multi-Function Contact Output 2 (terminal M3-M4)

bit 2

Multi-Function Contact Output 3 (terminal M5-M6)

bit 3 to 5

Reserved

bit 6

Enables the function in bit 7

bit 7

Fault Contact Output (terminal MA/MB-MC)

bit 8 to F

Reserved

000AH to 000CH Reserved

000DH

PI2 Setpoint

000EH

Reserved

000FH

Control Selection Setting
bit 0

Reserved

bit 1

PI Setpoint Input

bit 2, bit 3

Reserved

bit 4

PI2 Target Input (enables the setting from MEMOBUS/Modbus)

bit 5 to B

Reserved

bit C

Enable Terminal S5 Input for Broadcast Data

bit D

Enable Terminal S6 Input for Broadcast Data

bit E

Enable Terminal S7 Input for Broadcast Data

bit F

Reserved

0010H to 001FH

Reserved

D.9 MEMOBUS/Modbus Data Table

388

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

Advertising