Bypass enclosures, Bypass product options, Bypass, drive models, and capacities – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 30

Advertising
background image

n

Bypass, Drive Models, and Capacities

Bypass Unit

Model Z1B1

Output Capacity

Drive Model

CIMR-ZU

Electrical Schematic

Weight (lb)

HP

Input (A)

Output (A)

208 Vac

D002

0.5

2.9

2.4

2A0011

DD.Z1B1.W1.01

45.0

D003

0.75

4.0

3.5

D004

1

5.1

4.6

D007

2

8.0

7.5

D010

3

11.1

10.6

D016

5

17.2

16.7

2A0017

D024

7.5

24.7

24.2

2A0024

DD.Z1B1.W2.01

53.0

D030

10

31.3

30.8

2A0031

D046

15

46.7

46.2

2A0046

DD.Z1B1.W3.01

75.0

D059

20

59.9

59.4

2A0059

D074

25

75.5

74.8

2A0075

DD.Z1B1.W4.01

128.0

D088

30

88.7

88.0

2A0088

DD.Z1B1.W5.01

243.0

D114

40

114.7

114.0

2A0114

D143

50

144.4

143.0

2A0143

DD.Z1B1.W6.01

370.0

D169

60

170.4

169.0

2A0169

D211

75

212.4

211.0

2A0211

DD.Z1.1.F1.02

1050.0

D273

100

274.4

273.0

2A0273

480 Vac

B001

0.75

1.8

1.6

4A0005

DD.Z1B1.W1.01

45.0

B002

1

2.3

2.1

B003

2

3.6

3.4

B004

3

5.0

4.8

B007

5

7.8

7.6

4A0008

B011

7.5

11.2

11.0

4A0011

B014

10

14.2

14.0

4A0014

DD.Z1B1.W2.01

53.0

B021

15

21.2

21.0

4A0021

B027

20

27.2

27.0

4A0027

B034

25

34.2

34.0

4A0034

DD.Z1B1.W3.01

75.0

B040

30

40.2

40.0

4A0040

B52L

40

52.0

52.0

4A0052ooB

B052

40

52.2

52.0

4A0052ooA

DD.Z1B1.W4.01

128.0

B065

50

65.3

65.0

4A0065

B077

60

77.3

77.0

4A0077

B096

75

96.3

96.0

4A0096

DD.Z1B1.W5.01

243.0

B124

100

124.3

124.0

4A0124

B156

125

156.6

156.0

4A0156

DD.Z1B1.W6.01

370.0

B180

150

180.6

180.0

4A0180

B240

200

240.6

240.0

4A0240

DD.Z1.1.F1.02

1050.0

B302

250

302.6

302.0

4A0302

DD.Z1.1.F1.01

u

Bypass Enclosures

All Z1000 Bypass units are intended for non-hazardous locations. All Z1000 Bypass units are NEMA Type 1 Enclosures and

are constructed for indoor use to provide a degree of protection against incidental contact with enclosed electrical equipment

and falling dust or dirt.

u

Bypass Product Options

Refer to Bypass Options on page 305

for details on available bypass product configuration options.

1.3 Model Numbers and Nameplate Checks

30

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

Advertising