A.2 Drive Specifications

Note:

1. Perform rotational Auto-Tuning to obtain the performance specifications given below.
2. For optimum performance life of the drive, install the drive in an environment that meets the required specifications.

Table A.5 Specifications

Item

Specification

Control

Character-

istics

Control Method

V/f Control (V/f)

Frequency Control Range

0.01 to 240 Hz

Frequency Accuracy

(Temperature Fluctuation)

Digital input: within ±0.01% of the max output frequency (-10 to +50 °C)

Analog input: within ±0.1% of the max output frequency (25 °C ±10 °C)

Frequency Setting Resolution

Digital inputs: 0.01 Hz

Analog inputs: 1/1000 of the maximum output frequency setting (10 bit unsigned)

Output Frequency Resolution

0.001 Hz

Frequency Setting Signal

0 to 10 V, 0 to 20 mA, 4 to 20 mA

Starting Torque

<1>

140% at 3 Hz

Speed Control Range

<1>

1:40

Accel/Decel Time

0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)

Braking Torque

Approximately 20%

V/f Characteristics

User-selected programs and V/f preset patterns possible

Main Control Functions

Momentary Power Loss Ride-Thru, Speed Search, Overtorque/Undertorque Detection, 4 Step Speed (max),

Accel/Decel Switch, S-curve Accel/decel, 3-Wire Sequence, Auto-Tuning (Stationary for Line-to-Line

Resistance, Rotational for V/f Control), Cooling Fan on/off Switch, Slip Compensation, Torque

Compensation, Frequency Jump, Upper/lower Limits for Frequency Reference, DC Injection Braking at Start

and Stop, Overexcitation Braking, High Slip Braking, PI Control (with sleep function), Energy Saving

Control, MEMOBUS/Modbus Comm. (RS-422/RS-485 max, 115.2 kbps), BACnet Comm. (RS-485 max.

115.2 kbps), Fault Restart, Application Presets, KEB, Overexcitation Deceleration, Overvoltage

Suppression, Sequence Timer Operation, Secondary PI Control, Bypass Operation, HOA Keypad, Dynamic

Noise Control

Protection Functions

Motor Protection

Electronic thermal overload relay

Momentary Overcurrent

Protection

Drive stops when rated output current exceeds 175%

Overload Protection

Drive stops after 60 s at 110% of rated output current

<2>

Drive stops after 0.5 s at 140% of rated output current

<2>

Overvoltage Protection

208 V: Stops when DC bus voltage exceeds approx. 410 V

480 V: Stops when DC bus voltage exceeds approx. 820 V

Undervoltage Protection

208 V: Stops when DC bus voltage falls below approx. 190 V

480 V: Stops when DC bus voltage falls below approx. 440 V

Momentary Power Loss

Ride-Thru

Immediately stop after 15 ms or longer power loss

<3>

Heatsink Overheat Protection

Thermistor

Stall Prevention

Stall Prevention is available during acceleration, deceleration, and during run.

Ground Protection

Electronic circuit protection

<4> <5>

DC Bus Charge LED

Remains lit until DC bus voltage falls below 50 V

Environment

Area of Use

Indoors

Ambient Temperature

-10 °C to +40 °C NEMA Type 1 Enclosure

Humidity

95% RH or less (no condensation)

Storage Temperature

-20 °C to 70 °C (short-term temperature during transportation)

Altitude

Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.

Refer to Altitude

Derating on page 304

for details.

Vibration/Shock

10 to 20 Hz at 9.8 m/s

2

20 to 55 Hz at 5.9 m/s

2

(Drive models CIMR-Zo2A0011 to 2A0031 and 4A0005 to 4A0027) or

2.0 m/s

2

(Drive Models CIMR-Zo2A0046 to 2A0396 and 4A0034 to 4A0590)

Safety Standard

IEC/EN 61800-5-1

Protection Design

NEMA Type 1 enclosure

<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors

and with changing motor temperature. Contact Yaskawa for consultation.

<2> Overload protection may be triggered when operating with 100% of the rated output current if the output frequency is less than 6 Hz.
<3> May be shorter due to load conditions and motor speed.

A.2 Drive Specifications

300

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

Advertising