Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 243

Advertising
background image

HOA Keypad Display

Minor Fault Name

oH

Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02 (90-100 °C).

Default value for L8-02 is determined by drive capacity (o2-04).

Cause

Possible Solutions

Surrounding temperature is too high

• Check the surrounding temperature.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool surrounding area.
• Remove anything near drive that may cause extra heat.

Internal cooling fan has stopped

• Replace the cooling fan.
• After replacing the drive, set parameter o4-03 to 0 to reset the cooling fan operation time.

Airflow around the drive is restricted

• Provide proper installation space around the drive as indicated in the manual.

Refer to Installation

Orientation and Spacing on page 41

for details.

• Allow for the proper space and ensure that there is sufficient circulation around the control panel.
• Check for dust or other foreign materials clogging the cooling fan.
• Clear debris caught in the fan that restricts air circulation.

HOA Keypad Display

Minor Fault Name

oH2

Drive Overheat Warning

Cause

Possible Solutions

An external device triggered an overheat warning

in the drive

Search for the device that tripped the overheat warning. Remove the cause of the problem.

HOA Keypad Display

Minor Fault Name

oH3

Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level

(H3-02 or H3-10 = E).

Cause

Possible Solutions

Motor thermostat wiring is faulty (PTC input).

Repair the PTC input wiring.

There is a fault on the machine side (e.g., the

machine is locked up)

• Check the status of the machine.
• Remove the cause of the fault.

Motor has overheated

• Check the load size, accel/decel times, and cycle times.
• Decrease the load.
• Increase accel and decel times (C1-01 and C1-02).
• Adjust the preset V/f pattern. Set E1-03 to 6.
• Check the motor-rated current.
• Enter motor-rated current on motor nameplate (E2-01).
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.

HOA Keypad Display

Minor Fault Name

oL3

Overtorque 1
Drive output current was greater than L6-02 for longer than the time set to L6-03.

Cause

Possible Solutions

Inappropriate parameter settings

Check parameters L6-02 and L6-03.

There is a fault on the machine side (e.g., the

machine is locked up)

• Check the status of the machine.
• Remove the cause of the fault.

HOA Keypad Display

Minor Fault Name

ov

DC Bus Overvoltage
The DC bus voltage exceeded the trip point.
• For 208 V: approximately 410 V
• For 480 V: approximately 820 V

Cause

Possible Solutions

Surge voltage present in the drive input power

• Install an AC reactor.
• Voltage surge can result from a thyristor convertor and a phase advancing capacitor operating on

the same drive input power system.

6.5 Alarm Detection

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

243

6

Diagnostics & Troubleshooting