Main circuit terminal functions, Wire gauge and tightening torque specifications – Yaskawa AC Drive Z1000 Bypass Technical Manual User Manual

Page 62

Advertising
background image

u

Main Circuit Terminal Functions

Table 3.1 Main Circuit Terminal Functions

Terminal

Description

Function

Page

R/L1

Main circuit power supply input

Connects line power to the bypass

52

S/L2

T/L3
U/T1

Drive output

Connects to the motor

52

V/T2

W/T3

For 208 Vac: 100 Ω or less

For 480 Vac: 10 Ω or less

Grounding terminal

64

u

Wire Gauge and Tightening Torque Specifications

Note:

1. For 0 to 100 A, use a minimum of 60 °C - 75 °C copper wire.
2. For above 100 A, use a minimum of 75 °C copper wire.
3. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-sheathed wire assuming ambient

temperature within 40 °C and wiring distance less than 100 m.

• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is greater

than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following formula to

calculate the amount of voltage drop:
Line drop voltage (V) = 3 × wire resistance (Ω/km) × wire length (m) × current (A) × 10

-3

Refer to UL Standards Compliance on page 439

for information on UL compliance.

Table 3.2 Main Input Circuit Wiring Tightening Torques and Wire Gauges

Z1000 Bypass

Model Z1B1

With Option PM Circuit Breaker CB1

Standard Non-Fused Input Disconnect Switch S1

208

Vac

480

Vac

Current Rating

(A)

Wire Size Range

(AWG)

Tightening

Torque (lb. in.)

Current Rating

(A)

Wire Size Range

(AWG)

Tightening

Torque (lb. in.)

D002

B001

30

14-10

or

8-3/0

50

or

120

20

14-8

19

D003

B002

D004

B003

D007

B004

D010

B007

D016

B011

B014

B021

45

12-6

40

D024

B027

50

D030

B034

63

6-2

50

B040

100

B52L

100

8-2/0

200

D046

B052

D059

B065

B077

150

8-3/0

120

B096

150

D074

115

8-2/0

200

D088

150

8-3/0

120

D114

175

4-4/0

225

B124

250

4-40

225

D143

B156

3/0-350 kcmil

225

250

3/0-350 kcmil

225

D169

B180

3.4 Input and Output Power Wiring Connections

62

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual

Advertising