b5-14: PI Feedback Low Detection Time

Sets the time that the PI feedback has to fall below b5-13 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-14

PI Feedback Low Detection Time

0.0 to 25.5 s

1.0 s

n

b5-36: PI Feedback High Detection Level

Sets the feedback level used for PI feedback high detection. The PI feedback must exceed this level for longer than the time

set to b5-37 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-36

PI Feedback High Detection Level

0 to 100%

100%

n

b5-37: PI Feedback High Detection Time

Sets the time that the PI feedback must exceed the value set to b5-36 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-37

PI Feedback High Detection Time

0.0 to 25.5 s

1.0 s

<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.

n

PI Sleep/Snooze

The PI Sleep/Snooze function stops the drive when the PI output or the frequency reference falls below the PID Sleep/Snooze

operation level for a certain time. The drive will resume operating when the PI output or frequency reference rise above the

PI Sleep/Snooze operation level for the specified time. An example of PI Sleep/Snooze operation appears in the figure below.

PI Output

PI Sleep/Snooze
Level (b5-15)

Sleep Delay Time

Sleep Delay Time

Run command enabled

Continues to output “During Run”

Internal Run

command

External Run

command

During Run

Stop

b5-16

b5-16

Run

Figure 5.14 PI Sleep/Snooze Operation

Notes on Using the PI Sleep/Snooze Function

• The PI Sleep/Snooze function is active even when PI control is disabled.
• The PI Sleep/Snooze function stops the motor according to the stopping method set to b1-03.
The PI Snooze Function is a variation on the Sleep Function. Set b5-21 to 2 to select the PI Snooze function. After selecting

the Snooze Function, the drive monitors the output frequency. If the output frequency drops below the PI Snooze Level b5-22

<1>

), and stays below that level for at least the time set to b5-23

<1>

, PI Snooze Delay Time, the drive output shuts off.

The Snooze Function differs from the Sleep Function in that the feedback must drop below the level set to b5-24

<1>

, PI Snooze

Deactivation Level, before normal drive output will begin again. Immediately prior to Snooze Function activation, the PI

Setpoint can be temporarily increased to create an overshoot of the intended PI Setpoint. The temporary boost is determined

by parameter b5-25

<1>

, PI Boost Setting Level.

After reaching the temporary boost level (or exceeding the time set to b5-26, PI Maximum Boost Time), the drive output shuts

off (snoozes) and the intended PI Setpoint returns. From this point on, the Snooze Function operates normally and the drive

output returns when the feedback level drops below b5-24

<1>

.

<1> Details on this function can be found in the standard Z1000 Programming Manual (SIEPC71061645) at

www.yaskawa.com.
The parameters necessary to control the PI Sleep/Snooze Function are explained below.

5.2 b: Application

134

YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual