Register No.

Contents

8440H

Time HHMM

Time Hours and Minutes. Reads current time. Format is HHMM where HH is hours from 00 to 23

and MM is minutes from 00 to 59. Reads 0x0000 when no RTC option

8441H

Date Year

Date Year. Reads current date. Format is YYYY where YYYY is the year from 0000 to 9999.

Reads 0x0000 when there is no RTC option.

8442H

Date Mo Day MMDD

Date Month and Day. Reads current date. Format is MMDD where MM is month from 01 to12

and DD is day from 01 to 31. Reads 0x0000 when there is no RTC option

8443H to 84FFH

Reserved

8490H

Product Type Code

8491H

Product Type Code

8500H to 87FFH

BYP Parameters and

Monitors

Z1-oo, Z2-oo, Z3-oo, Z4-oo , UB-oo.

Refer to Parameter List on page 307

for Modbus

addresses.

8800H to FFFFH

Reserved

<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> Communication error contents are saved until the fault is reset.
<3> The number of decimal places in the parameter value depends on the drive model.

Refer to Defaults by Drive Model on page 351

for details.

<4> Set the number of motor poles to parameter E2-04 or E5-05 depending on the motor being used.
<5> Disabled when Z3-12 is set to 0 in bypass controller software versions VST800298 and later.

u

Broadcast Messages

Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not

respond.

Register No.

Contents

0001H

Digital Input Command
bit 0

Forward Run (0: Stop 1: Run)

bit 1

Direction Command (0: Forward, 1: Reverse)

bit 2, bit 3

Reserved

bit 4

External Fault

bit 5

Fault Reset

bit 6 to B

Reserved

bit C

Multi-Function Digital Input S5

bit D

Multi-Function Digital Input S6

bit E

Multi-Function Digital Input S7

bit F

Reserved

0002H

Frequency Reference

30000/100%

u

Fault Trace Contents

The table below shows the drive fault codes that can be read out by MEMOBUS/Modbus commands from the U2-oo monitor

parameters.

Table D.3 Fault Trace / History Register Contents

Fault Code

Fault Name

0002H

Undervoltage (Uv1)

0003H

Control Power Supply Undervoltage (Uv2)

0004H

Soft Charge Circuit Fault (Uv3)

0006H

Ground Fault (GF)

0007H

Overcurrent (oC)

0008H

Overvoltage (ov)

0009H

Heatsink Overheat (oH)

000AH

Heatsink Overheat (oH1)

000BH

Motor Overload (oL1)

Fault Code

Fault Name

000CH

Drive Overload (oL2)

000DH

Overtorque Detection 1 (oL3)

0010H

Braking Resistor Overheat (rH)

0011H

External Fault at Input Terminal S3 (EF3)

0012H

External Fault at Input Terminal S4 (EF4)

0013H

External Fault at Input Terminal S5 (EF5)

0014H

External Fault at Input Terminal S6 (EF6)

0015H

External Fault at Input Terminal S7 (EF7)

001BH

Input Phase Loss (PF)

D.9 MEMOBUS/Modbus Data Table