Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 105

Advertising
background image

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

105

Drive Port 0 Parameters

Chapter 3

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Rea

d-Write

Da

ta T

ype

PR

OTE

CTION

Pr

edi

cti

ve

Main

te

n

an

ce

469

PredMaint Sts
Predictive Maintenance Status

RO

16-bit
Integer

Status of predictive maintenance elapsed life relative to the programmed event level. A value of 1 = event level has been exceeded. Bit 15 is a master bit which = 1
when 1 or more individual bits = 1.

470

PredMaintAmbTemp
Predictive Maintenance Ambient Temperature
Used to predict cooling fan life, and possibly the life of other temperature dependent
components in the future. Changes to this parameter affect the total life and remaining
life, meaning that only one temperature can be programmed for the entire life of the
drive.

Units:
Default:
Min/Max:

DegC
50.00
0.00 / 50.00

RW Real

471

PredMaint Rst En
Predictive Maintenance Reset Enable
Enables P472 [PredMaint Reset] to execute a reset of the selected elapsed life
parameter. Any single reset in P472 [PredMaint Reset] will force this parameter back to 0
(disabled), so that only one elapsed life parameter can be reset at a time.
This parameter is only reset when Set Defaults “All” (not recommended) is executed.

Default:
Options:

Current Selection
0 = “Disable”
1 = “Enable”

RW 32-bit

Integer

472

PredMaint Reset
Predictive Maintenance Reset
Resets predictive maintenance elapsed life parameters, one at a time. Enabled by P471
[PredMaint Rst En].
This parameter is only reset when Set Defaults “All” (not recommended) is executed.

Default:
Options:

Current Selection
0 = “Ready”
1 = “HS Fan Life”

(1)

2 = “In Fan Life”

(1)

3 = “MtrBrng Life”
4 = “MtrLube Hrs”
5 = “MchBrng Life”
6 = “MchLube Hrs”

(1)

Frames 1…7 only.

RW 32-bit

Integer

481

CbFan Derate

Cabinet Fan Derate
Derating factor applied to P482 [CbFan TotalLife]. Used to adjust total fan life for poor air
quality or vibration.

Default:
Min/Max:

1.00
0.01 / 1.00

RW Real

482

CbFan TotalLife

Cabinet Fan Total Life
Total number of hours expected over the life of a single cabinet fan. Calculated as a
function of fan manufacturer's life data (from frame rating table), P470
[PredMaintAmbTemp] and P481 [CbFan Derate].

Units:
Default:
Min/Max:

Hrs
0.00
0.00 / 21474836.47 (31 bits)

RO

32-bit
Integer

483

CbFan ElpsdLife

Cabinet Fan Elapsed Life
Accumulated hours of cabinet fan run time.
Frame 8 drives have a single converter, and therefore a single cabinet fan. The value of
this parameter reflects the elapsed life of that fan.
Frame 9 drives have two converters, and therefore two cabinet fans. Frame 10 drives
have three converters, and therefore three cabinet fans. For frame 9 and 10 drives, the
value of this parameter reflects the longest elapsed life of all the cabinet fans. Individual
elapsed life values are available at parameters 138 [C1 CbFanElpsdLif], 238 [C2
CbFanElpsdLif], and 338 [C3 CbFanElpsLif] in port 11.

Units:
Default:
Min/Max:

Hrs
0.00
0.00 / 21474836.47 (31 bits)

RO

32-bit
Integer

Options

Mast

er

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Mch L

ube

Mch Be

arin

g

Mtr L

ube

Mtr

B

ear

in

g

In

te

rn

al

F

an

He

at

si

nk F

an

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = False
1 = True

755 (8+)

755 (8+)

755 (8+)

Advertising