Troubleshooting

Chapter 6

Drive will not reverse motor direction.

Stopping the drive results in a Decel Inhibit fault.

Problems adding a datalink.

Cause(s)

Indication

Corrective Action

Digital input is not selected for reversing
control.

None

Check that the DI Reversing function is correctly
configured.

Digital input is incorrectly wired.

None

Check digital input wiring.

Direction mode parameter is incorrectly
programmed.

None

Reprogram P308 [Direction Mode],

page 85

for

analog “Bipolar” or digital “Unipolar” control.

Motor wiring is improperly phased for
reverse.

None

Switch two motor leads.

A bipolar analog speed command input
is incorrectly wired or signal is absent.

None

1. Use meter to check that an analog input voltage is

present.

2. Check bipolar analog signal wiring.
Positive voltage commands forward direction.
Negative voltage commands reverse direction.

Cause(s)

Indication

Corrective Action

The bus regulation feature is enabled
and is halting deceleration due to
excessive bus voltage. Excess bus
voltage is normally due to excessive
regenerated energy or unstable AC line
input voltages.
Internal timer has halted drive
operation.

Decel Inhibit fault
screen.
LCD Status Line
indicates
“Faulted.”

1. Reprogram parameters 372/373 [Bus Reg Mode n]

to eliminate any “Adjust Freq” selection.

2. Disable bus regulation (parameters 372/373 [Bus

Reg Mode n]) and add a dynamic brake.

3. Correct AC input line instability or add an isolation

transformer.

4. Access P409 [Dec Inhibit Actn] to select desired

fault action.

5. Reset drive.

Cause(s)

Indication

Corrective Action

Another device is communicating with
the processor.

None

1. Verify that DeviceLogix is not running (Port 14, P53

[DLX Operation] = 5 “Logic Disabled.”)

2. Verify that a PLC is not communication with the

drive. Disconnect communication cable or inhibit
communication in PLC software.