Drive (port 0) applications file – Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 172

Advertising
background image

172

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 3

Drive Port 0 Parameters

Drive (Port 0) Applications
File

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

APPLIC

AT

ION

S

Proces

s P

ID

1065

PID Cfg
PID Configuration

RW 16-bit

Integer

Main configuration of the Process PID controller.

Bit 0 “Preload Int” – Preload the PID integral term with PID Preload value.
Bit 1 “Ramp Ref” – Ramp PID Reference when first enabled.
Bit 2 “Zero Clamp” – Clamp PID output to zero when P1079 [PID Output Sel] is set to option 2 “Speed Trim” or 4 “Torque Trim.”
Bit 3 “Fdbk Sqrt” – Apply Square root function to the Feedback signal.
Bit 4 “Stop Mode” – When P1079 [PID Output Sel] is set to option 2 “Speed Trim,” PID remains active during stopping maneuver.
Bit 5 “Anti Windup” – Prevents PID integrator from getting too far ahead of frequency ramp.
Bit 6 “Percent Ref” – When P1079 [PID Output Sel] is set to option 2 “Speed Trim,” PID output is a percentage of the Speed Reference versus a percentage of P27
[Motor NP Hertz].

1066

PID Control
PID Control

RW 16-bit

Integer

Used for dynamically controlling the Process PID controller.

Bit 0 “PID Enable” – PID controller is enabled.
Bit 1 “PID Hold” – Hold PID integrator.
Bit 2 “PID Reset” – Reset PID integrator.
Bit 3 “PID InvError” – Invert PID error.

1067

PID Ref Sel
PID Reference Select
Selects the source for the PID Reference.

Default:
Min/Max:

1070
1 / 159999

RW 32-bit

Integer

1068

PID Ref AnlgHi
PID Reference Analog High
When an analog input is selected for PID Ref this sets high value of scaling.

Units:
Default:
Min/Max:

%
100.00
–/+100.00

RW Real

1069

PID Ref AnlgLo
PID Reference Analog Low
When an analog input is selected for PID Ref this sets low value of scaling.

Units:
Default:
Min/Max:

%
0.00
–/+100.00

RW Real

1070

PID Setpoint
PID Setpoint
Provides an internal fixed value for PID Ref when P1067 [PID Ref Sel] is set to this
parameter.

Units:
Default:
Min/Max:

%
0.00
–/+100.00

RW Real

1071

PID Ref Mult
PID Reference Multiplier
Sets the multiplying factor which is applied to the Reference source before the
Reference is used.

Units:
Default:
Min/Max:

%
100.00
–/+100.00

RW Real

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Pe

rc

en

t R

ef

Anti W

indup

Stop

Mo

de

Fdbk Sqr

t

Ze

ro

Cl

am

p

Ra

mp Ref

Pr

el

oa

d I

nt

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Disabled
1 = Enabled

Options

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

Rese

rv

ed

PI

D I

nv

Err

or

PI

D R

ese

t

PID Hol

d

PI

D Ena

ble

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Condition False
1 = Condition True

Advertising