333

I1 Comm Loss
I2 Comm Loss
I3 Comm Loss

Resettable
Fault

Coast

A communications fault has occurred between the main control board
and the power layer interface board on inverter n.

341
342
343

C1 Comm Loss
C2 Comm Loss
C3 Comm Loss

Resettable
Fault

Coast

A communications fault has occurred between the main control board
and the converter gate board on converter n.

351
352
353

In Cur Share L1
In Cur Share L2
In Cur Share L3

Alarm 1

There is an input current sharing imbalance between parallel converters
in the AC line indicated that is greater than 15% of the converter rated
current.

357
358
359

In Vlt Imbal L12
In Vlt Imbal L23
In Vlt Imbal L31

Alarm 1

There is a input line voltage imbalance between parallel converters in
the AC lines indicated that is greater than 5% of the converter rated
voltage.

360

N-1 See Manual

Resettable
Fault

Coast

The number of active inverters has been reduced from the original
parallel configuration.
Refer to

N-1 and Re-Rate Functions on page 341

.

361

Rerate See Manual

Resettable
Fault

Coast

The drive rating has changed from the original parallel configuration.
Refer to

N-1 and Re-Rate Functions on page 341

.

362

Cnv/Inv Mismatch

Alarm 2

There is a voltage class mismatch between the installed parallel
inverters and converters.

363

CBP/Inv Mismatch

Alarm 2

There is a voltage class mismatch between the installed parallel
inverters and common DC bus precharge units.

364

CBP Num Mismatch

Alarm 2

The number of active inverters and active common DC bus precharge
units does not match.

365

Zero Cnv/Prechrg

Alarm 2

No converter or common DC bus precharge unit exists.

366

Cnv Num Mismatch

Alarm 2

The number of active inverters and active converters does not match.

371
372

P1 Comm Loss
P2 Comm Loss

Resettable
Fault

Coast

A communications fault has occurred between the main control board
and the DC precharge control board on the common DC bus precharge
unit n.

380

PWM FPGA Overrun

Alarm 1

The time limit on the PWM write to the FPGA was exceeded.

900

900

Resettable
Fault

Coast

Critical input exception.
Cycle power to clear this fault. Contact technical support.

901

Machine Check

Resettable
Fault

Coast

Internal error.
Replace the main control board.

902

Data Storage Error

Resettable
Fault

Coast

Cache memory corrupt.
Replace the main control board.

903

Instruction Storage Error

Resettable
Fault

Coast

Cache memory corrupt.
Replace the main control board.

905

Alignment Error

Resettable
Fault

Coast

Pointer is pointing to a non-boundary member.
Obtain test points and check grounding.

906

Program Error

Resettable
Fault

Coast

Bad memory read.
Check grounding or replace the main control board.

907

Floating Point Unit Not
On

Resettable
Fault

Coast

Firmware issue.
Obtain test points.

909

Aux Processor Not On

Resettable
Fault

Coast

Auxiliary processor interrupt.
Cycle power to clear this fault. Contact technical support.

912

Watchdog

Resettable
Fault

Coast

Timer counted down, reached 0, and fault occurred.
Replace the main control board.

913

Data TLB Error

Resettable
Fault

Coast

Processor attempted to access non-boundary memory.
Check grounding or replace the main control board.

914

Instruction TLB Error

Resettable
Fault

Coast

Processor attempted to access non-boundary memory.
Check grounding or replace the main control board.

Event
No.

Fault/Alarm Text

Type

Fault
Action

Configuration
Parameter

Auto
Reset

Description/Action(s)