Drive Port 0 Parameters

Chapter 3

SPEED C

O

NTRO

L

Speed Re

fe

re

nce

592

Selected Spd Ref
Selected Speed Reference
Displays the value of the active speed reference.

Units:

Default:
Min/Max:

Hz
RPM
0.00
–/+P27 [Motor NP Hertz]
–/+P28 [Motor NP RPM]

RO

Real

593

Limited Spd Ref
Limited Speed Reference
Displays the value of the speed reference after the following limits have been applied:
P520 [Max Fwd Speed], P521 [Max Rev Speed], P522 [Min Fwd Speed] and P523 [Min
Rev Speed].

Units:

Default:
Min/Max:

Hz
RPM
0.00
–/+P27 [Motor NP Hertz]
–/+P28 [Motor NP RPM]

RO

Real

594

Ramped Spd Ref
Ramped Speed Reference
Displays the output of the speed reference ramp and S-curve functions, but prior to any
corrections added by slip comp, PI, etc.

Units:

Default:
Min/Max:

Hz
RPM
0.00
–/+P27 [Motor NP Hertz]
–/+P28 [Motor NP RPM]

RO

Real

595

Filtered Spd Ref
Filtered Speed Reference
Displays the output of the filter that is applied by P588 [Spd Ref Filter].

Units:

Default:
Min/Max:

Hz
RPM
0.00
–/+P27 [Motor NP Hertz]
–/+P28 [Motor NP RPM]

RO

Real

596

Speed Rate Ref
Speed Rate Reference
This parameter is shared by both the Inertia Compensation and Speed Compensation
functions. These functions are only available in the Flux Vector selections for P35 [Motor
Ctrl Mode].
A value shared by both the Inertia Compensation and Speed Compensation functions
(active only in FV motor control modes), typically supplied by an external controller that
is also providing a rate limited speed reference. The Speed Rate Reference corresponds
to the derivative with respect to time of the speed reference signal. Units of time are in
seconds.
For example, if the controller provides a 10 second reference ramp, the controller would
also supply a Speed Rate Ref value of 1 pu / 10 sec = 0.1 sec-1 while the reference is
accelerating. When the reference is constant, Speed Rate Ref should be zero.

Units:

Default:
Min/Max:

Hz
RPM
0.00
–/+P27 [Motor NP Hertz]
–/+P28 [Motor NP RPM]

RW Real

597

Final Speed Ref
Final Speed Reference
Displays the speed reference value, after all reference modifications (including ramps),
that is used as a final reference by the speed regulator. In Open Loop, Sensorless Vector
mode, this value represents the anticipated motor operating speed, and may differ
slightly from the output frequency value due to slip compensation.

Units:

Default:
Min/Max:

Hz
RPM
0.00
–/+P27 [Motor NP Hertz]
–/+P28 [Motor NP RPM]

RO

Real

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

SPEED C

O

NTROL

Speed T

rim

600
604

Trim Ref A Sel
Trim Ref B Sel
Trim Reference A, B Select
Selects a trim source (in Hz or RPM) for Speed Reference A or Speed Reference B,
respectively. For trim in % instead of Hz or RPM, use P608/612 (TrimPct Refn Sel).

Default:

Min/Max:

P601 [Trim Ref A Sel]
P605 [Trim Ref B Stpt]
0 / 159999

RW 32-bit

Integer

601
605

Trim Ref A Stpt
Trim Ref B Stpt
Trim Reference A, B Setpoint
A digital value to be used as a possible trim source for P600 or P604, respectively

Units:

Default:
Min/Max:

Hz
RPM
0.00
–/+P27 [Motor NP Hertz]
–/+P28 [Motor NP RPM]

RW Real