Predictive Maintenance for Floor Mount Drives (Frames 8…10)

There can be multiple power structures in parallel on floor mount drives; and
therefore, multiple sets of fans, which make the predictive maintenance more
complicated than on wall mount drives.

To minimize the number of parameters, the parallel inverters, converters, and
precharge units do not have separate [Total Life] and [Remaining Life]
parameters. The user must calculate the individual [Remaining Life] values in the
controller.

A frame 10 drive has three power structures, and three sets of cabinet fans,
heatsink fans, and internal stirring fans.

These parameters are available for the cabinet fans.

Table 3 - Cabinet Fan Parameters

The user must calculate the [Remaining Life] parameter values for the cabinet
fans in each power structure. This is needed anytime the [Elapsed Life] parameter
of one power structure differs from another. This difference can occur when one
power structure has been replaced or serviced separately from the others.

Node

Parameter No.

Parameter Name

Description

0

482

CBFan TotalLife

Displays the expected lifespan for a cabinet fan.

0

483

CBFan ElpsdLife

Displays the greatest expended life of a cabinet fan.

0

484

CBFan RemainLife

Displays the difference between P482 [CBFan TotalLife] and
P483 [CBFan ElpsdLife].

11

138

C1 CBFanElpsdLife

Displays the expended life of the fans on cabinet 1.

11

238

C2 CBFanElpsdLife

Displays the expended life of the fans on cabinet 2.

11

338

C3 CBFanElpsdLife

Displays the expended life of the fans on cabinet 3.

C1

Cabinet Fans

C2

Cabinet Fans

C3

Cabinet Fans

Power Structure

1

Power Structure

2

Power Structure

3