Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 6

Troubleshooting

78

FluxAmpsRef Rang

Alarm 2

The default for P70 [Autotune] is 1 “Calculate” and the value for flux
amps determined by the Autotune procedure exceeds the value
programmed in P26 [Motor NP Amps].
Check motor nameplate data against parameters P25 [Motor NP Volts]
through P30 [Motor NP Power].

Resettable
Fault

Coast

P70 [Autotune] is set to 2 “Static Tune” or 3 “Rotate Tune” and the value
for flux amps measured by the Autotune procedure exceeds the value
programmed in P26 [Motor NP Amps].

79

Excessive Load

Resettable
Fault

Coast

The motor did not come up to speed in the allotted time during
Autotune.

80

AutoTune Aborted

Resettable
Fault

Coast

The Autotune function was manually canceled or a fault occurred.

81
82
83
84
85
86

Port 1 DPI Loss
Port 2 DPI Loss
Port 3 DPI Loss
Port 4 DPI Loss
Port 5 DPI Loss
Port 6 DPI Loss

Resettable
Fault

Coast

324

[Logic Mask]

The DPI port stopped communicating.
Check connections and drive grounding.

87

IXo VoltageRange

Alarm 2

The default for P70 [Autotune] is 1 “Calculate” and the voltage
calculated for motor inductive impedance exceeds 25% of the value of
P25 [Motor NP Volts].

Resettable
Fault

Coast

P70 [Autotune] is set to 2 “Static Tune” or 3 “Rotate Tune” and the
voltage measured for motor inductive impedance exceeds 25% of the
value of P25 [Motor NP Volts].

91

Pri VelFdbk Loss

Configurable

Note: See option module
for configuration
parameter number

A Feedback Loss has been detected for the source of P127 [Pri Vel
Feedback]. This could be due to a problem detected by the feedback
option module selected by P125 [Pri Vel Fdbk Sel] or due to a loss in
communication between the feedback option module and main control
board. The source of primary velocity feedback must be configured not
to fault if the feedback loss switchover feature is used.

93

Hw Enable Check

Resettable
Fault

Coast

Hardware enable is disabled (jumper installed) but indicates not
enabled.

94

Alt VelFdbk Loss

Configurable

Note: See option module
for configuration
parameter number

A Feedback Loss has been detected for the source of P128 [Alt Vel Fdbk
Sel]. This could be due to a problem detected by the feedback option
module selected by P128 [Alt Vel Fdbk Sel] or due to a loss in
communication between the feedback option module and main control
board.

95

Aux VelFdbk Loss

Configurable

Note: See option module
for configuration
parameter number

A Feedback Loss has been detected for the source of P132 [Aux Vel Fdbk
Sel]. This could be due to a problem detected by the feedback option
module selected by P132 [Aux Vel Fdbk Sel] or due to a loss in
communication between the feedback option module and main control
board.

96

PositionFdbkLoss

Configurable

Note: See option module
for configuration
parameter number

A Feedback Loss has been detected for the source of P847 [Psn Fdbk].
This could be due to a problem detected by the feedback option module
selected by P135 [Mtr Psn Fdbk Sel] or due to a loss in communication
between the feedback option module and main control board.

97

Auto Tach Switch

Resettable
Fault

Coast

635

[Spd Options Ctrl]

Bit 7 “Auto Tach SW”

Indication that either of the two following conditions exists.
Tach switch has occurred and alternate feedback device has failed.
Tach switch has not occurred, Auto Tach Switch Option is enabled and

both primary and alternate devices have failed.

100

Parameter Chksum

Resettable
Fault

Coast

The checksum read from the non-volatile storage does not match the
checksum calculated. Data set to default value.

101

PwrDn NVS Blank

Resettable
Fault

Coast

Internal data error.
Reset parameter defaults. See publication

20HIM-UM001

for

instructions.

Reload parameters.
If problem persists replace main control board.
Fault normally occurs after a flash update to correct F117 fault.