Chapter 3

Drive Port 0 Parameters

Drive (Port 0) Torque Control
File

Fil

e

Gr

oup

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

TO

RQUE C

O

NTROL

To

rq

u

e L

im

it

s

670

Pos Torque Limit
Positive Torque Limit
Defines the torque limit for the positive torque reference value. The reference will not be
allowed to exceed this value.
Only active in Flux Vector (FV) motor control modes (P35).

Units:
Default:
Min/Max:

%
200.00
0.00 / 800.00

RW Real

671

Neg Torque Limit
Negative Torque Limit
Defines the torque limit for the negative torque reference value. The reference will not
be allowed to exceed this value.
Only active in Flux Vector (FV) motor control modes (P35).

Units:
Default:
Min/Max:

%
–200.00
–800.00 / 0.00

RW Real

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

TO

RQUE C

O

NT

ROL

To

rq

ue

R

ef

er

en

ce

675
680

Trq Ref A Sel
Trq Ref B Sel
Torque Reference A, B Select
Selects the source for a torque reference, used when the drive is configured to command
torque according to P309…312 [SpdTrqPsn Mode n]. The values of the torque reference
sources are added together to provide a single torque reference.
Only active in Flux Vector (FV) motor control modes (P35).

Default:

Min/Max:

676
681
0 / 159999

RW 32-bit

Integer

676
681

Trq Ref A Stpt
Trq Ref B Stpt
Torque Reference A, B Setpoint
A digital torque value to be used as a possible source for P675 and P680 respectively.
Only active in Flux Vector (FV) motor control modes (P35).

Units:
Default:
Min/Max:

%
0.00
–/+800.00

RW Real

677
682

Trq Ref A AnlgHi
Trq Ref B AnlgHi
Torque Reference A, B Analog High
Used only when an analog input is selected as a torque reference according to P676 or
P681. Sets the torque value that corresponds to P51/61 [Anlg Inn Hi] on an I/O module
or on the main control (product dependent). This establishes scaling throughout the
range.
Only active in Flux Vector (FV) motor control modes (P35).

Units:
Default:
Min/Max:

%
100.00
–/+800.00

RW Real

678
683

Trq Ref A AnlgLo
Trq Ref B AnlgLo
Torque Reference A, B Analog Low
Used only when an analog input is selected as a torque reference according to P676 or
P681. Sets the torque value that corresponds to P52/62 [Anlg Inn Lo] on an I/O module
or on the main control (product dependent). This establishes scaling throughout the
range.
Only active in Flux Vector (FV) motor control modes (P35).

Units:
Default:
Min/Max:

%
0.00
–/+800.00

RW Real

679
684

Trq Ref A Mult
Trq Ref B Mult
Torque Reference A, B Multiplier
A multiplier that is applied to the values referenced by P675 and P680 respectively. A
value of 1 leaves the reference unaffected. Negative values invert the reference.
Only active in Flux Vector (FV) motor control modes (P35).

Default:
Min/Max:

1.000
–/+1000.000

RW Real