Fine Tuning

P1195 [Pump Off Level], P1196 [Pump Off Speed], and P1197 [Pump Off
Time] all contribute to the productivity of the well and need to be adjusted. For
more information read the parameter descriptions in

Chapter 3

.

Occasionally the position starts to drift relative to the torque signature. If this
occurs, set P1188 [Pump Off Setup] Bit 1 “Pos Offset” to 1. See

Figure 78

for an

example of what this drift would look like.

Figure 78 - Correcting Drift

Notice how the position has drifted relative to the torque causing a different part
of the waveform to be averaged as the down stroke torque. This drift results in a
false pump off condition. Setting the position offset bit corrects this drift.

Sleep Mode

If P1189 [Pump Off Action] is set to 1 “Always Stop,” 2 “Stop After 1,” or 3 “Stop
After 2,” the Sleep Wake function must be configured. Set the following
parameters.

Parameter

Setting

Start Features

P350 [Sleep Wake Mode]

1 “Direct” (Enabled)

P351 [SleepWake RefSel]

1207 (Entered through the Numeric Edit tab.)

P355 [Wake Time]

Desired restart time (64800 seconds maximum).