Drive Port 0 Parameters

Chapter 3

FEEDBA

CK

&

I/O

D

igi

tal O

utput

s

244

TO0 On Time

Transistor Output 0 On Time
Sets the “ON Delay” time for the digital outputs. This is the time between the occurrence
of a condition and activation of the relay or transistor.

Units:
Default:
Min/Max:

Secs
0
0 / 159999

RW 32-bit

Integer

245

TO0 Off Time

Transistor Output 0 Off Time
Sets the “OFF Delay” time for the digital outputs. This is the time between the
disappearance of a condition and de-activation of the relay or transistor.

Units:
Default:
Min/Max:

Secs
0.0
–/+1000000.0

RW Real

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype

753

753

Fil

e

Gr

ou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-Write

Da

ta

T

yp

e

FEEDBA

CK & I/O

M

otor P

TC

250

PTC Cfg

Positive Temperature Coefficient Configuration
Sets the action that will be taken when the PTC is indicating over temperature.
“Ignore” (0) – No action is taken.
“Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.

Default:
Options:

0 – Ignore
0 – Ignore
1 – Alarm
2 Flt Minor
3 FltCoastStop
4 Flt RampStop
5 Flt CL Stop

RW 32-bit

Integer

251

PTC Sts

Positive Temperature Coefficient Status

RO

16-bit
Integer

Status of the PTC.

Bit 0 “PTC Ok” – PTC is within the acceptable temperature range.
Bit 2 “Over Temp” – PTC is indicating over temperature

753

753

Options

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Re

ser

ve

d

Ov

er

Te

m

p

Re

ser

ve

d

PT

C O

k

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Condition False
1 = Condition True

Fil

e

Gro

u

p

No.

Display Name
Full Name
Description

Values

Read-W

ri

te

Da

ta

T

yp

e

FEEDBA

CK & I/O

An

al

og In

puts

255

Anlg In Type

Analog Input Type

RO

16-bit
Integer

Status of the analog input mode set by Jumper J4 on the main control board.

753

Options

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Re

se

rv

ed

Analog 0

Default

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Bit

15 14 13 12 11 10 9

8

7

6

5

4

3

2

1

0

0 = Voltage Mode
1 = Current Mode