xx023

Ch0 AccCode Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Incorrect access code

xx024

Ch0 FieldSizeErr

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Size of data field stated cannot be changed

xx025

Ch0 Address Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Word address stated is outside data field

xx026

Ch0 FieldAcc Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Access to non-existent data field

xx028

Ch0 SiTurnPsnErr

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Single turn position unreliable

xx029

Ch0 MulTrnPsnErr

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Multiple turn position unreliable

xx036

Ch0 AnalVal Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Analog value error (process data)

xx037

Ch0 SendCurr Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Transmitter current critical (dirt, broken transmitter)

xx038

Ch0 EncTemp Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Encoder temperature critical

xx039

Ch0 Speed Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by Stegmann Encoder on Channel 0 with Hiperface
Interface - Speed too high, no position formation possible

xx040

Ch0 General Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by a Encoder on Channel 0 with BiSS Interface - An error
bit of the BiSS Single Cycle Data is set

xx046

Ch0 LED Curr Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by a Encoder on Channel 0 with BiSS Interface - LED
current out of control range

xx047

Ch0 ExMulTurnErr

Configurable

P9
[FB0 Loss Cfg]

Error reported by a Encoder on Channel 0 with BiSS Interface - External
multiturn error

xx048

Ch0 PsnCode Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by a Encoder on Channel 0 with BiSS Interface - Position
code error (single step error)

xx049

Ch0 Config Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by a Encoder on Channel 0 with BiSS Interface - failure
configuring interface

xx050

Ch0 PsnVal Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by a Encoder on Channel 0 with BiSS Interface - Position
data not valid

xx051

Ch0 SerialComErr

Configurable

P9
[FB0 Loss Cfg]

Error reported by a Encoder on Channel 0 with BiSS Interface - Serial
interface failure

xx052

Ch0 Ext Failure

Configurable

P9
[FB0 Loss Cfg]

Error reported by a Encoder on Channel 0 with BiSS Interface - External
failure over NERR

xx053

Ch0 Temp Exc Err

Configurable

P9
[FB0 Loss Cfg]

Error reported by a Encoder on Channel 0 with BiSS Interface -
Temperature out of defined range

xx058

Module Defaulted

Fault

Coast

Parameter values for this encoder have been reset to their default
settings.

xx064

Ch0 OutOfRailErr

Configurable

P9
[FB0 Loss Cfg]

Error reported by a linear Stahl encoder on Channel 0 - Rail is no longer
present between the read head

xx068

Ch0 Read Head 1

Configurable

P9
[FB0 Loss Cfg]

Error reported by a linear Stahl encoder on Channel 0 - Indicates that the
read head must be cleaned or installed correctly

xx069

Ch0 Read Head 2

Configurable

P9
[FB0 Loss Cfg]

Error reported by a linear Stahl encoder on Channel 0 - Indicates that the
read head must be cleaned or installed correctly

xx070

Ch0 RAM Error

Configurable

P9
[FB0 Loss Cfg]

Error reported by a linear Stahl encoder on Channel 0 - Indicates a RAM
error. Reading head needs to be repaired

xx071

Ch0 EPROM Error

Configurable

P9
[FB0 Loss Cfg]

Error reported by a linear Stahl encoder on Channel 0 - Indicates a
EPROM error. Reading head needs to be repaired

Event
No.

(1)

Fault/Alarm Text

Type

Fault
Action

Configuration Param

Auto
Reset

Description