Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual

Page 20

Advertising
background image

20

Rockwell Automation Publication 750-PM001J-EN-P - October 2014

Chapter 1

Start Up

Figure 2 - Setting the IP Address Switches

Possible Settings

Description

000

Adapter will use, depending on P36 [BOOTP], the BOOTP setting or the adapter parameter
settings for the IP address.

001…254

Adapter will use the rotary switch settings for the IP address (192.168.1.xxx, where xxx =
rotary switch settings).

255…887

Adapter will use, depending on P36 [BOOTP], the BOOTP setting or the adapter parameter
settings for the IP address.

888

Resets the adapter IP address function to factory defaults. Thereafter, the drive must be
powered down, the switches set to a setting other than 888, and then the drive must be
powered up again to accept the new address.

889…998

Adapter will use, depending on P36 [BOOTP], the BOOTP setting or the adapter parameter
settings for the IP address.

999
(default settings)

Disables the rotary switches. Adapter will use, depending on P36 [BOOTP], the BOOTP
setting or the adapter parameter settings for the IP address.