Rockwell Automation 21G PowerFlex 750-Series AC Drives Programming Manual User Manual
Page 220

220
Rockwell Automation Publication 750-PM001J-EN-P - October 2014
Chapter 4
Port 10 and Port 11 Parameters
Fil
e
Gr
ou
p
No.
Display Name
Full Name
Description
Values
Re
ad
-Write
Da
ta T
ype
INVERTER N
Predi
ct
iv
e M
ain
127
227
327
I1 PredMainReset
I2 PredMainReset
I3 PredMainReset
Inverter n Predictive Maintenance Reset
Allows a reset of the elapsed run time to zero for either the heatsink fan or internal
stirring fans for inverter n. After the time has been reset, the value of this parameter
returns to 0 “Ready.”
“Hs Fan Life” (1) – Resets the elapsed run time (displayed in [In HSFanElpsdLif]) for the
heatsink fan on inverter n to zero.
“In Fan Life” (2) – Resets the elapsed run time (displayed in [In InFanElpsdLif]) for the
internal stirring fans on inverter n to zero.
Default:
Options:
0 = “Ready”
0 = “Ready”
1 = “HS Fan Life”
2 = “In Fan Life”
RW 32-bit
Integer
128
228
328
I1 HSFanElpsdLif
I2 HSFanElpsdLif
I3 HSFanElpsdLif
Inverter n Heatsink Fan Elapsed Life
The amount of time the heat sink fan on inverter n has been running. This value can be
reset using [In PredMainReset].
Units:
Default:
Min/Max:
Hrs
0.00
0.00 / 220000000.00
RO
Real
129
229
329
I1 InFanElpsdLif
I2 InFanElpsdLif
I3 InFanElpsdLif
Inverter n Internal Fan Elapsed Life
The amount of time the inverter stirring fans on inverter n have been running. This value
can be reset using [In PredMainReset].
Units:
Default:
Min/Max:
Hrs
0.00
0.00 / 220000000.00
RO
Real
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
Fil
e
Gr
oup
No.
Display Name
Full Name
Description
Values
Read-W
rite
Da
ta
T
yp
e
INVERTER N
Te
st
po
in
ts
140
142
240
242
340
342
I1 Testpt Sel 1
I1 Testpt Sel 2
I2 Testpt Sel 1
I2 Testpt Sel 2
I3 Testpt Sel 1
I3 Testpt Sel 2
Inverter n Testpoint Selection 1, 2
Selects a source for [In Testpt Val n]. Used by the factory, typically for diagnostic
purposes.
Default:
Min/Max:
0
0 / 65535
RW 32-bit
Integer
141
143
241
243
341
343
I1 Testpt Val 1
I1 Testpt Val 2
I2 Testpt Val 1
I2 Testpt Val 2
I3 Testpt Val 1
I3 Testpt Val 2
Inverter n Testpoint Value 1, 2
Displays the data selected by [In Testpt Sel n].
Default:
Min/Max:
0.000000
–/+220000000.000000
RO
Real
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)
755 (8+)