Chapter 3

Drive Port 0 Parameters

MO

TO

R

C

O

NT

ROL

Ve

ctor Re

gu

lator

106

Trq Adapt Speed
Torque Adaption Speed
Operating frequency (speed) at which the adaptive torque control regulators become
active as a percent of motor nameplate frequency. This selection is active only in motor
control mode flux vector induction (P35 [Motor Ctrl Mode] = 3 “Induction FV”).

Units:
Default:
Min/Max:

%
10.00
0.00 / 100.00

RW Real

107

Trq Adapt En
Torque Adaption Enable
Enables or disables the adaptive torque control. This selection is active only in motor
control mode flux vector induction (P35 [Motor Ctrl Mode] = 3 “Induction FV”).

Default:
Options:

1 – Enabled
0 – Disabled
1 – Enabled

RW 32-bit

Integer

108

Phase Delay Comp
Phase Delay Compensation
Used to adjust the sample delay compensation gain for the current feedback. The gain
compensation is scaled to the sample time (for example, +1.0 would be a compensation
of positive 1 sample time).

Default:
Min/Max:

0.00
–/+100.00

RW Real

109

Trq Comp Mode
Torque Compensation Mode
Automatic: Updates the torque compensation gains (P110 [Trq Comp Mtring] and P111
[Torque Comp Regen]) after autotune.

Default:
Options:

1 – Auto
0 – Manual
1 – Auto

RW 32-bit

Integer

110

Trq Comp Mtring
Torque Compensation Motoring
Motor torque compensation applied to the torque command for motoring power. This
parameter can be set manually or determined automatically during autotune. (See P109
[Trq Comp Mode].) In manual mode, a value of 5% will increase the commanded torque
by 5% (gain of 1.05). This is used for flux vector motor control mode (P35 [Motor Ctrl
Mode] = 3 “Induction FV”).

Units:
Default:
Min/Max:

%
0.00
–/+50.00

RW Real

111

Trq Comp Regen
Torque Compensation Regeneration
Motor torque compensation applied to the torque command for regenerating torque.
This parameter can be set manually or determined automatically during autotune. (See
P109 [Trq Comp Mode].) In manual mode, a value of -3% will decrease the commanded
torque by 3% (gain of 0.97). This is used for flux vector motor control modes (P35 [Motor
Ctrl Mode]).

Units:
Default:
Min/Max:

%
0.00
–/+50.00

RW Real

112

Slip Adapt Iqs
Slip Adaption Iqs
Level of per unit Iqs at which the adaptive slip frequency regulator becomes active.
Active when P35 [Motor Ctrl Mode] = 3 “Induction FV.”

Default:
Min/Max:

0.05
0.00 / 1.00

RW Real

113

SFAdapt SlewLmt
Slip and Flux Adaption Slew Limit
Time that the slip, flux, and torque regulators are allowed to converge before the
regulators are turned on after the motor speed reaches the level set in P106 [Trq Adapt
Speed]. Active when P35 [Motor Ctrl Mode] = 3 “Induction FV.”

Units:
Default:
Min/Max:

Secs
0.00
0.00 / 60.00

RW Real

114

SFAdapt SlewRate
Slip and Flux Adaption Slew Rate
Rate that the slip and flux regulators can converge before the regulators are enabled.
Active when P35 [Motor Ctrl Mode] = 3 “Induction FV.”

Default:
Min/Max:

0.004999
0.000009 / 1.000000

RW Real

115

SFAdapt CnvrgLvl
Slip and Flux Adaption Converge Level
Slip and flux regulator error level that indicates convergence. Active when P35 [Motor
Ctrl Mode] = 3 “Induction FV.”

Default:
Min/Max:

0.009999
0.000009 / 1.000000

RW Real

116

SFAdapt CnvrgLmt
Slip and Flux Adaption Converge Limit
Duration of convergence before the adaption regulators are enabled after the error has
decreased below the level set in P115 [SFAdapt CnvrgLvl]. Active when P35 [Motor Ctrl
Mode] = 3 “Induction FV.”

Default:
Min/Max:

0.500
0.000 / 5.000

RW Real

120

See

page 63

.

Fi

le

Grou

p

No.

Display Name
Full Name
Description

Values

Re

ad

-W

ri

te

Da

ta

T

ype